Delta Electronics AC Motor Drive VFD007S23A User Manual page 101

Delta electronics ac motor drive user manual
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-S Series
d29 M0: 0: RUN 1: STOP, M1: no function, Direction is controlled by keypad
4-09
Line Start Lockout
Settings
When enabled, the AC drive will not start when powered up with run commands applied. To
start in Line Start Lockout mode, the AC drive must see the run command go from stop to run
after power up. When Line Start Lockout is disable (also known as Auto-Start), the drive will
start when powered-up with run commands applied.
4-10
Up/Down Mode
Settings
Accel/Decel Rate of Change of UP/DOWN Operation
4-11
with Constant Speed
Settings
This parameter is used to set the acceleration/deceleration speed mode when multi-function
terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15, d16)
5-46
RUN/STOP
GND
d0
Disable
d1
Enable
d0
Based on accel/decel time
d1
up frequency according to constant speed, down frequency
according to deceleration time
d2
up frequency according to acceleration time, down frequency
according to constant speed
d3
Constant speed
d0 to d1000 Hz/sec
M0 "Open": Stop, "Close": Run
M1 No Function
Factory Setting: d0
Factory Setting: d0
Factory Setting: d1
Revision August 2006, SE08, SW V2.61
Unit: 5