SIMPLIFIED TAG DIAGNOSTICS
Tag diagnostics is only available in Modbus TAGs Gateway mode.
Tag diagnostics can also be viewed via the Modbus serial and Ethernet ports: via special Modbus registers.
The first Modbus address, from which the simplified diagnostics starts, is by default 49001 (Holding Register
9000).
Each bit represents a tag with the following meaning:
1 = TAG OK
0 = TAG FAIL
The least significant bit is the status of tag no. 1
The next is the status of tag no. 2 and so on ...
For example the reading of the following registers:
49001
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
49002
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1
Means: TAG 1, TAG 4, TAG17, TAG 18 , TAG 19, TAG 20 OK, all the others in FAIL.
At the start, all tags are in a fail state (all 0).
EXTENDED TAG DIAGNOSTICS
Tag diagnostics is only available in Modbus TAGs Gateway mode.
When a tag is in an error state it is possible to get more information using extended diagnostics.
Extended diagnostics reserves 1 byte for each tag (since the limit is 500 tags, there are 500 bytes = 250 Modbus
registers for extended diagnostics).
This diagnostics is found at the end of the simplified diagnostics (default starting Modbus address is 49033,
Holding register 32).
Each Modbus register contains 2 tags, so for example:
49033 TAG02_TAG01
49034 TAG04_TAG03
...
49282 TAG500_TAG499
49283 LAST_LOOP_TIME_COM1
49284 LAST_LOOP_TIME_COM2
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
User Manual
[x1 ms]
[x1 ms]
www.seneca.it
MODBUS TO CLOUD
"KEY-C" GATEWAYS
MI00725-1-EN
Page 16
Need help?
Do you have a question about the KEY-C Series and is the answer not in the manual?