On-site configuration
To connect a gateway, observe the technical documentation of the
gateway and the connection accessories.
4
On-site configuration
4.1
DIP switch setting
WARNING
Risk to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before working on electrical parts, disconnect all phases of the
power supply (fuse/circuit breaker) and lock the isolator switch to
prevent unintentional reconnection.
All DIP switches have been configured before delivery. The default
setting is highlighted bold.
▶ Only professional maintenance personnel should change these
settings.
▶ Improper DIP switch settings may cause condensation, noise, or
unexpected system malfunction.
Definition of DIP switch 0/1:
Definition 0
Definition 1
Table 65 Switch positions
ENC1
Code
0
1
2
4
5
7
8
9
A
B
1) Default depending on the model
Table 66 Set the output
54
1)
Capacity setting
20
26
32 - 35
36 - 53
54 - 71
72 - 90
91 - 105
109 - 140
141 - 160
161 - 200
S1
S1 Setting
0 - F
0 - F
0 - F
0 - F
1) Default
Table 67 Set the network address
DIP switch
Definition of DIP Switches
Fan OFF temperature when heating (anti-cold air function)
SW1
• [00]: 0°
• [01]: 15°C
• [10]: 8°C
• [11]: Reserved
Behaviour of the fan once the room target temperature has been
reached
SW2
• [0]: Fan off
• [1]: Fan on (anti-cold air function deactivated)
Auto restart
SW3
• [0]: Automatic restart on
• [1]: Automatic restart off
Set master and slave unit
SW5
• [00]: Master unit only, no slave unit
• [01]: Master unit (heating)
• [10]: Master unit (cooling)
• [11]: Slave unit
Temperature compensation (heating)
SW6
• [00]: 0 °C
• [01]: 2°C
• [10]: 4°C
• [11]: Reserved
1) Default highlighted in bold
Table 68 Definition of DIP Switches
Climate 5000 L • Climate 5000iL – 6721841494 (2024/06)
S2
Network address
1)
0 - 15
16 - 31
32 - 47
48 - 63
1)