Advertisement
Carrier's Comfort Pro programmable thermostats are wallmounted, low-voltage thermostats that maintain room temperature by controlling the operation of a heating and/or air conditioning system (Fig. 1).
Fig. 1 — Comfort Pro Programmable Commercial Thermostat
The thermostat can be used with a heat pump, air conditioner or water source heat pump operation. A variety of features are provided including battery operation, separate heating and cooling set points, auto changeover, keypad lockout, backlighting, and built-in installer test.
The programming interface is a one touch interface, with the comfort selections Occupied, Unoccupied, and Limit (Energy Savings Mode). The user can adjust the heating and/or cooling set points for each of the three comfort selections.
This Installation Instruction covers installation, configuration, and start-up of the Comfort Pro thermostat. For operational details, consult the Owner's Manual for this specific thermostat.
1 — Thermostat
1 — Backplate (mounting base)
2 — Screws and anchors
The thermostat will obtain full operating power one of two ways: full 24 volt AC (50/60 Hz) power via the Rc/ Rh and C terminals or two AA alkaline batteries. The 24 vac operation is preferred, if available. Battery operation is used when there are not enough wires to support 24 vac operation. When the battery is low, a Low Battery indication will be displayed to the user.
For an AC system, up to six wires are needed for 24 vac operation and one less wire for battery operation. For a heat pump system, up to seven wires are needed for 24 vac operation and one less wire would be sufficient for battery operation. For heat only operation with batteries, only two wires are required (R and W). When battery operation is used, the C terminal does not need to be connected.
Provision is also made for separate heating and cooling transformers via separable Rc and Rh terminals which are connected via factory-installed jumper wire.
The wire length should be no more than 250 ft (76 m). Use 22 AWG (American Wire Gage) for normal wiring applications. Continuous wire lengths over 100 ft (30.5 m) should use 20 AWG or larger.
The thermostat should be mounted:
The thermostat should NOT be mounted:
To install the thermostat, perform the following procedure:
When power is applied, all display icons are lit for 2 seconds to test the display. Following this, the equipment type for which the thermostat is configured is displayed for an additional 2 seconds. Equipment type will be either HP, AC, H, C or 35 (for water source heat pump [WSHP]) (see explanation for Option 01 below).
NOTE: If a common wire has not been connected, two AA batteries must be used to power the thermostat.
Configuration options enable the installer to configure the thermostat for a particular installation. These configuration options are stored to the internal memory so they are retained through a power outage. The availability of some configuration options will be dependent upon other conditions in the thermostat. For example, the backlight configuration is not available unless full 24 vac power is connected. See Table 1.
Table 1 — Configuration Options Summary
OPTION NUMBER | CONFIGURATION |
01 | Equipment Type |
02 | Remote Sensor Selection |
03* | English/Metric |
04 | Fan (G) on with W Output |
05 | Space Temperature Sensing |
07 | Equipment DDC Controller |
10 | Reversing Valve |
11 | Deadband between Heating and Cooling Set Points |
12 | Smart Recovery |
13 | Space Temperature Display Adjustment (Offset) |
15 | Auto Mode Availability |
16 | Maximum Cycles Per Hour |
17 | Time Between Equipment Stages |
18* | Backlight Configuration |
20 | Outdoor Air Temperature Adjustment (Offset) |
21 | Keypad Lockout |
24 | Programmable/Non-Programmable |
25 | Number of programmable periods per day |
26 | Minimum Cooling Set Point |
27 | Maximum Heating Set Point |
35 | Emergency Heat Mode Availability |
36 | Fan Selection |
38 | Override Timer Maximum |
39 | Temperature Display |
99 | Reset to Factory Defaults |
* These settings are adjustable by the user. See Owner's Manual for additional information.
The installer must set the time and date before the thermostat's programming features can be used. Perform the following procedure:
Press and hold the fan button for about 10 seconds. After the 10-second period the option number will appear in the heat set point location. The value of the configuration setting will be displayed in the cool set point location.
The parameter that is changeable will be determined by the flashing area. The up or down button can be used to select a new value. The mode button can be used to toggle/move the selection between the configuration option number and the configuration value. To exit the installer configuration screen, press the fan button. If no button is pressed for three minutes, the installer configuration screen will time out and the thermostat will return to normal operation.
All changes to the installer configuration are saved as they are made. There is no provision to exit the installer configuration and cancel the change. The installer will have to manually change a configuration back to its original value to "undo" a change.
OPTION 01 — EQUIPMENT TYPE — This option determines the control method of the thermostat. It should match the type of equipment used.
Selection: HP, AC, H, C, 35
HP — operates a two-stage heat pump
AC — operates a two-stage AC
H — operates a heat only system
C — operates a cool only system
35 — operates a water source heat pump
Default: AC
OPTION 02 — REMOTE SENSOR SELECTION — A remote thermistor can be connected to the S1 and S2 screw terminals to sense either remote space, outdoor air, supply or return air temperature.
NOTE: Carrier sensors 33ZCT55SPT, 33ZCSENDAT, 33ZCSENSAT, and 33ZCSENOAT may be used for standard space temperature sensor averaging. Sensors must be used as a single sensor, 4 sensors or 9 sensors, with total sensor wiring not to exceed 1,000 feet.
Selection: rS, SA, Od, rA
rS — sense remote space temperature
SA* — sense supply air temperature
Od* — sense outdoor air temperature
rA* — sense return air temperature
* Display only, not used for temperature control.
Default: Od
OPTION 03 — ENGLISH/METRIC — This configuration selects between Fahrenheit (F) and Celsius (C) operation.
Selection: F, C
Default: F
OPTION 04 — FAN (G) ON WITH W OUTPUT — This configuration is not available if the thermostat is configured as Cool Only in Option 01. This selection determines whether fan (G) output is to be on or off when the W is energized in AC, HP, H or 35 (WSHP) configurations, and when the O/B output is energized in the AC or H (heat only) configurations.
Selection: OF(F), ON
OF — fan does not turn on with W output
ON — fan turns on with W output
Default: ON
OPTION 05 — SPACE TEMPERATURE SENSING — This selection determines which sensor the control will use for measuring space temperature. Space temperature can be sensed in one of three ways: the local sensor (L) located on the thermostat, the remote sensor (r), or the average of local and remote sensors (Lr).
Selection: L, r, Lr
L — Local Sensor: The onboard thermistor is the control point for the temperature control algorithm.
r — Remote Space sensor: The remote space temperature is the control point for the temperature control algorithm.
NOTE: This selection is only available if Option 02 indicates that the S1, S2 terminals are sensing a remote space temperature.
Lr — The average of the onboard thermistor and the remote space sensor is the control point for the temperature control algorithm.
NOTE: This selection is only available if Option 02 indicates that the S1, S2 terminals are sensing a remote space temperature.
When this value is changed, the Space Temperature Display Adjustment Offset (Option 13) is reset to zero. Default: L
OPTION 07 — EQUIPMENT DDC CONTROLLER — This selection should be set to ON when control is to be used with DDC (direct digital controller) equipment. These control systems will take care of the time guard and cycle timers. Examples are zone controlling units or two-position valve assemblies that can open or close as required, without regard to exceeding a maximum number of operations per hour. Rooftop units used with PremierLink™ or ComfortLink controls do not require thermostat control to handle timers and safeties, so this selection would also be set to ON in this case.
Set this selection to OF (off) if the thermostat is directly connected to equipment such as a furnace or fan coil unit with DX condensing units, or electro-mechanical rooftop units that have a maximum number of cycles per hour rating, but do not implement that requirement themselves and rely instead on the thermostat.
Selection: OF(F), ON
OF — timeguard and cycle timers are enabled
ON — timeguard and cycle timers are disabled
Default: OF (off)
OPTION 10 — REVERSING VALVE — This feature is only available on heat pump (HP) systems. Although the water source heat pump is also a heat pump system, a WSHP system will always energize the reversing valve in cooling. The "O/B" terminal can be configured to be energized in either heating mode or in cooling mode, depending on heat pump operation.
The "C" configuration is used to describe a heat pump system that energizes its reversing valve in cooling. The "H" configuration is used to describe a heat pump system that energizes its reversing valve in heating.
Selection: H, C
H — The reversing value output (O/B) is energized when HEAT mode is selected.
C — The reversing value output (O/B) is energized when COOL mode is selected.
Default: H
OPTION 11 — DEADBAND BETWEEN HEATING AND COOLING SET POINTS — The selection allows the installer to choose how much differential will exist between the heating and cooling set points.
Selection: 1 to 10 (F or C)
Default: 5
OPTION 12 — SMART RECOVERY — Smart recovery is a function that transitions the space to the next programmed heating and cooling set points as energy efficiently as possible.
OF (off) means set points change precisely at setback recovery time. A value of 30, 60, or 90 selects the number of minutes that recovery starts before programmed recovery time. Recovery takes place smoothly during the selected recovery time, ending at the recovery time and temperature which is programmed. The HOLD function needs to be off in order for this to work correctly.
Selection: OF, 30, 60, 90
Default: 90
OPTION 13 — SPACE TEMPERATURE DISPLAY ADJUSTMENT (OFFSET) — This configuration is the number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured space temperature. This selection is not available to the installer if Option 39 is set to SP (set point display).
Selection: –5 to 5 F (always in F)
Default: 0
OPTION 15 — AUTO MODE AVAILABILITY — The ON selection will allow automatic changeover between heating and cooling as demand requires a mode selection. OF maintains either heating or cooling mode selection only. Auto changeover is not available when H or C is selected under Option 01.
Selection: ON, OF(F)
ON — Auto mode is an available option that can be selected
OF — Auto mode is not an available option
Default: ON
OPTION 16 — MAX CYCLES PER HOUR — The maximum cycle rate is limited by internal timers to the selected number of cycles per hour. Selection of a higher number causes faster cycling resulting in more constant room temperature.
Selection: 4, 6, 8
4 — The Y1 and W outputs will be energized at most twice per hour. When an output is energized, it will not be energized again for 15 minutes.
6 — The Y1 and W outputs will be energized at most four times per hour. When an output is energized, it will not be energized again for 10 minutes.
8 — The Y1 and W outputs will be energized at most six times per hour. When an output is energized, it will not be energized again for 8 minutes.
Default: 4
OPTION 17 — TIME BETWEEN EQUIPMENT STAGES — This configuration determines the minimum number of minutes of equipment operation before allowing the transition to the next logical stage.
NOTE: If the difference between the space air temperature and set point results in a demand greater than three degrees, then the staging timers are ignored and the equipment will stage up in 60-second increments.
Selection: 10, 15, 20, 25
Default: 15
OPTION 18 — BACKLIGHT CONFIGURATION — This function is only available when the thermostat is operating from 24 volt AC power connected to the R and C terminals. It is not available when the thermostat operates from batteries.
When set to OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off.
When ON is enabled, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs.
Selection: OF(F), ON
Default: ON with 24 vac power; for batteries only, default is OFF.
OPTION 20 — OUTDOOR AIR TEMPERATURE DISPLAY ADJUSTMENT (OFFSET) — This selection is not available unless Option 02 is set to Od (outdoor air temperature) and a valid sensor is connected to S1 and S2 terminals. It allows the calibration, or deliberate miscalibration of the outdoor air temperature sensor reading.
Selection: –5 to 5 (number of degrees F added to the outdoor air temperature reading to "calibrate" the temperature sensor)
Default: 0
OPTION 21 — KEYPAD LOCKOUT WITH PASS-CODE — The thermostats are shipped with the keypad fully accessible. This option allows the installer to limit access to the keypad. When this option is changed from OF to either 1, 2, 3 or cd, an access code will be need to be entered (see instructions below). Once entered, the thermostat will lock with that code and whatever security level (1, 2, 3 or cd) is selected by the installer as noted below.
NOTE: The option number and setting for code 21 will move to the large temperature display to allow the keypad code to be entered. The mode button will still move between the option number and the value setting. The OCC and LIMIT buttons in conjunction with the up or down button will facilitate code entry. Pressing the mode key at any time will return to the option value field (large digits).
Selection: OF(F), 1, 2, 3, cd
OF — User has full access to the keypad
1 — User has access to modify set points and time of day
2 — User can change set points only
3 — User cannot change any operating parameters
cd — Entire keypad is locked
1 — Without Unlock Code
To activate the locking code at level 1 without an unlock code, perform the following:
When this option is chosen, the user has access to modify the set points (within the set point limits of Option 26 and Option 27), and the time of day. The occupied (OCC) button will be functional. The hold button will be locked out. The padlock icon will be on until the user presses and holds up and down buttons simultaneously for five seconds to unlock the keypad. Once the keypad is unlocked, the user has full access to the thermostat functionality. The keypad returns to the locked condition after no buttons have been pressed for two minutes.
1 — With Code
To activate the locking code at level 1 with an unlock code, perform the following:
When this option is chosen, the thermostat will be completely locked and the padlock icon will be on steady. Once the unlock code has been entered and the done button is pressed, the padlock icon flashes and the thermostat functionality operates as described above in the "1 — Without Unlock Code" description.
2 — Without Unlock Code
To activate the locking code at level 2 without an unlock code, perform the following:
When this option is chosen, the user has access to change the set points only. The hold button will be locked out. The OCC button is functional. The padlock icon will be on until the user presses and holds the up and down buttons simultaneously for five seconds to unlock the keypad. Once the keypad is unlocked, the user has full access to the thermostat functionality. The keypad returns to the locked condition after no buttons have been pressed for two minutes.
2 — With Code
To activate the locking code at level 2 with an unlock code, perform the following:
When this option is chosen, the thermostat will be completely locked and the padlock icon will be on steady. Once the unlock code has been entered and the done button has been pressed, the padlock icon flashes and the thermostat functionality operates as described above in the "2 — Without Unlock Code" description.
3 — Without Unlock Code
To activate the locking code at level 3 without an unlock code, perform the following:
When this option is chosen, the entire keypad will be locked. When the user presses a button, the backlight turns on to maximum brightness for 10 seconds but none of the thermostat operating parameters can be changed. The padlock icon will be on until the user presses and holds the up and down buttons simultaneously for five seconds to unlock the keypad. Once the keypad is unlocked the user has full access to the thermostat functionality. The keypad returns to the locked condition after no buttons have been pressed for two minutes.
3 — With Code
To activate the locking code at level 3 with an unlock code, perform the following:
When this level is chosen, the thermostat will be completely locked and the padlock icon will be on steady. Once the unlock code has been entered and the done button has been pressed, the padlock icon flashes and the thermostat functionality operates as described above in the "3 — Without Unlock Code" description.
cd — Code Only
To activate the locking code at level cd (code only), perform the following:
When this level is chosen, the entire keypad will be locked and the padlock icon will be displayed. When the user presses a button, the backlight turns on to maximum brightness for 10 seconds and a "-- --" is shown in the clock display. The user enters the unlock code and presses the done button to unlock the thermostat. The padlock icon turns off and the user has full access to the thermostat functionality. The thermostat locks after no buttons have been pressed for two minutes.
The following applies to all levels of keypad lockout other than OFF:
In the event that the installer or user cannot remember the unlock code for the thermostat, the code can be displayed if the user presses and holds the days and the set clock simultaneously for 30 seconds. After the 30-second period, the unlock code will be displayed for five seconds. This information does not appear in any other user documentation.
Default: OF (off)
OPTION 24 — PROGRAMMABLE/NON-PROGRAMMABLE — This allows the installer to configure the thermostat to operate as either programmable or non-programmable. When nP is selected, the clock is displayed, but the program schedule, the hold, smart recovery and day of the week functionality are disabled. The "hold" and "temporary hold" icons are inactive.
Selection: P, nP
Default = P
OPTION 25 — NUMBER OF PROGRAMMABLE PERIODS — This allows the installer to configure the thermostat for two or four periods per day. This configuration is not available if Option 24 has been set to nP to configure the thermostat for non-programmable operation.
Selection: 2,4
2 — Periods P1 (OCC) and P2 (UNOCC) are available
4 — Periods P1 (OCC), P2 (OCC), P3 (OCC) and P4 (UNOCC) are available.
Default: 4
OPTION 26 — MINIMUM COOLING SET POINT — This parameter establishes the minimum cooling set point that the user is allowed to set. If the equipment type is Cool Only, the lower limit is 55 F and the upper limit is 90 F. Otherwise, the equipment type allows both heating and cooling operation, so the minimum is 55 F plus Option 11 (deadband) and the maximum is 90 F.
Selection: minimum = 55 F + deadband, maximum = 90 F
Default: 60 F (based on the adjustable deadband default = 5)
OPTION 27 — MAXIMUM HEATING SET POINT — This parameter establishes the maximum heating set point that the user is allowed to set. If the equipment type is Heat Only, the lower limit is 50 F and the upper limit is 90 F. Otherwise, the equipment type allows both heating and cooling operations, so the minimum is 50 F plus Option 11 (deadband) and the maximum is 90 F.
Selection: minimum = 50 F, maximum = 90 F – deadband
Default: 85 F (based on adjustable deadband default = 5)
OPTION 35 — EMERGENCY HEAT MODE AVAILABILITY — This configuration allows the installer to turn on or off the Em heat (emergency heat) mode. When set to ON, the emergency heat mode is an available mode selection. When set to OF, the emergency heat mode is not an available mode selection.
OPTION 36 — FAN SELECTION — This configuration allows the installer to configure the fan selection allowed during the occupied and unoccupied period.
When ON is selected, the fan will operate continuously during occupied periods, and during the unoccupied periods the fan will be set to auto to run only when the heating or cooling equipment is energized.
When OF(F) is selected, the user can adjust the fan setting between On and Auto for both occupied and unoccupied periods.
NOTE: The OF(F) selection is a violation of ASHRAE 90.1 and Title 24 but is a feature of the thermostat for building owners that mandate auto fan operation during occupied periods for energy conservation purposes. It is possible that an error code of E7 may appear on the screen if this option is set to ON and the user is trying to change the fan mode.
Selection: OF(F), ON
Default: ON
OPTION 38 — OVERRIDE TIMER MAXIMUM — This setting allows the installer to set the maximum override time between 0:15 and 6:00. The adjustment can be made in 15-minute increments. The maximum number of hours is 6:00.
Pressing the up button while in this configuration mode will increment the override time in 15-minute steps (15, 30, 45). The hours will increment during each pass through 00 minutes to a maximum setting of 6:00.
Pressing the down button while in this configuration mode will decrement the override time in 15 minute steps (45, 30, 15, 00). The hours will decrement during each transition from 45 to 00 to a minimum of 0:15.
Selection: 0:15 to 6:00
Default: 2:00 (two hours and zero minutes)
OPTION 39 — TEMPERATURE DISPLAY — This configuration allows the installer to select either the set point temperature or the space temperature to be displayed on the large temperature display digits.
When the option St is chosen, the space temperature, as defined by Option 05, is displayed using the traditional space temperature digits on the LCD display. The current set temperature is displayed using the normal set point display digits.
When SP is chosen, the current set point temperature is displayed using the traditional space temperature digits on the LCD display. The normal set point display digits remain blank. Space temperature is not displayed, but if a problem occurs with the actual space temperature sensor, the characters "- -" will be displayed instead of the set temperature to indicate that the temperature sensor has an error.
NOTE: The "Actual Temp" icon is not displayed when the sensor type is set to set point display (SP).
Selection: St, SP
Default: St Space Temperature
OPTION 99 — RESET TO FACTORY DEFAULTS — This configuration allows the installer to return the thermostat to its "out of the box" settings.
All configuration settings, modes, fan, and set point settings which have been manually entered will be lost and reset.
When this setting is first selected, "99" will be displayed in the space temperature location and an initial value of "10" will be displayed in the set point location.
To initiate factory defaults, the installer then presses the mode button until the 10 is flashing. The installer then presses and holds the down button. While the down button is held, the 10 will count down from 10 to 0. When the counter reaches zero, "Fd" is displayed in the large space temperature display area to note that factory defaults are in progress. When the factory defaults have been restored, the thermostat will act as if power was cycled (all display icons are lit for 2 seconds) and the clock will be flashing. Follow the instructions in the Setting Time and Day of Week section.
NOTE: If the down button is released early, the number will return to 10 and the reset will not occur.
This thermostat has a built-in installer test capability. It allows easy operation of equipment without delays or set point adjustments to force heating or cooling. To enter installer test mode, press and hold the fan button for about 15 seconds until the display reads "In" on the left and "St" on the right. The mode will be set to off. The mode button (upper left) can now be used to select heat, cool, or emergency heat. Selecting one of the available modes will immediately command the equipment to turn on in that mode. It will run for 3 minutes on equipment stage and then return the mode to off. The clock display counts down from 180 seconds while each stage operates. Changing the mode to off will terminate any running test immediately. During any test, the display icons will be displayed the same as for normal operation of that stage, as shown in Table 2.
Table 2 — Installer Test
SELECTED MODE | DISPLAY ICONS |
OFF | off |
COOL | cool on, 2 (for second stage cooling) |
HEAT | heat on, aux heat on |
EM HEAT | aux heat on |
To terminate the Installer Test mode, press the done button. After 15 minutes of no button presses by the installer, installer test is terminated.
The following installer checklist should be performed after completing installation:
Perform the following procedure to change the heating and/or cooling set points:
Perform the following procedure to temporarily override the program schedule:
Perform the following procedure to override the programmed temperature settings and hold the temperature at a specific setting:
To turn off the hold feature, press the hold/run button again. The set points will change to the program schedule values.
When the user presses the OCC, UNOCC, or LIMIT button, the preset temperature settings will be viewed and a triangle icon will appear above the OCC, UNOCC, or LIMIT button indicating which presets are being used.
The LIMIT button is used for an occupied period with settings that are less conditioned than the occupied (OCC) settings but more conditioned than the unoccupied (UNOCC) settings. This is used as an occupied energy savings function.
The default set points for the Comfort settings (OCC, UNOCC and LIMIT) are listed in Table 3.
Table 3 — OCC, UNOCC, and LIMIT Settings
ONE-TOUCH SETTING | HEAT SET POINT | COOL SET POINT |
OCC | 68 | 78 |
UNOCC | 60 | 85 |
LIMIT | 66 | 80 |
The set points for the OCC, UNOCC, and LIMIT OneTouch functions can be modified from their factory defaults using the following procedure:
The Comfort Pro programmable thermostat gives the user the option of programming for all days, weekdays or weekends. The thermostat is pre-programmed at the factory with the same settings for all seven days. See Table 4.
Table 4 — Schedule Factory Settings
PERIOD | START TIME | HEAT SET POINT | COOL SET POINT |
OCC | 6 AM | 68 | 78 |
OCC | 8 AM | 68 | 78 |
OCC | 3 PM | 68 | 78 |
UNOCC | 6 PM | 60 | 85 |
To set up different schedule, perform following procedure:
NOTE: Once a change is made to the programming schedule, it is saved when the user moves along to the next programming interval or level. Changes within a given programming period are considered temporary changes that require user confirmation by either closing the door or pressing the done button which would confirm any changes made up to that point.
The mode button allows the user to display the off, heat, cool, auto and emergency heat icons. Pressing the mode button cycles through the available modes based on the equipment selection from Option 01, the auto availability setting from Option 15, and the emergency heat availability from Option 35. Available choices are listed in Table 5.
Table 5 — Mode Selection
OPTION 01 (Equipment Selection) | OPTION 15 (Auto Available) | OPTION 35 (Emergency Heat Mode Available) | AVAILABLE MODES |
AC, HP or 35 (WSHP) | On | On | Off, Heat, Cool, Auto, Em Heat |
Off | Off, Heat, Cool, Auto | ||
Off | On | Off, Heat, Cool, Em Heat | |
Off | Off, Heat, Cool | ||
H | Not Available | On | Off, Heat, Em Heat |
Off | Off, Heat | ||
C | Not Available | Not Available | Off, Cool |
Immediately following a power cycle, the thermostat display will light all LCD segments for two seconds. During this process, the thermostat memory will be accessed to establish thermostat operating parameters.
Battery operation is available for installations where there is no common (C) wire available at the thermostat. For battery operation, install two alkaline AA batteries. The thermostat is designed to operate up to one year on a set of batteries. A battery indicator on the display warns when battery replacement is needed. If batteries are installed and the thermostat is operating from 24 vac power, battery operation will occur only when 24 vac power is not present. The changeover between 24 vac power and battery power is automatic.
The display has two levels of lighting, high level and low level. High level lighting comes on for 10 seconds when the door is opened and/or buttons are being pressed with 24 vac and with batteries. Low level lighting is only available if the thermostat is operated from 24 vac; it is not available with batteries. The low level can be selected (see Option 18) for continuous backlight.
When the door is opened, the display changes from its normal operation view. The large temperature display disappears so it will be available for other user functions. If the door is left open for 3 minutes, the display reverts to normal operation.
Pressing the up and down buttons simultaneously displays the temperature of the sensor connected to the S1 and S2 terminals and the sensor usage as defined by Option 02 in the cool set point display.
If the sensor is invalid, then the display will show "-" in the large temperature display digits and the cool set point display will be blank.
If the sensor is valid but Option 02 is set to rS and Option 39 is set to SP then the display will show "-."
Fig. 6 shows Option 02 set to outdoor air (Od) and the sensor temperature reading of 72 degrees. The remote sensor temperature will be displayed for five seconds and then the thermostat returns to normal operation.
Fig. 6 — Remote Sensor Temperature
Any buttons that are pressed while the remote sensor temperature is being displayed will be ignored.
NOTE: Carrier sensors 33ZCT55SPT, 33ZCSENDAT, 33ZCSENSAT, and 33ZCSENOAT may be used for standard space temperature sensor averaging. Sensors must be used as a single sensor, 4 sensors or 9 sensors, with total sensor wiring not to exceed 1,000 ft.
The remote space temperature 33ZCT55SPT sensor includes a button that, when pressed, shorts the S1 and S2 terminals. If the thermostat is powered by 24 vac and Option 02 is set to rS, pressing the button for two to five seconds has the same effect as an occupied button press on the thermostat. This button press is only recognized when the thermostat is powered by 24 vac.
For those installations requiring it, mounting hole locations for the programmable model are spaced to fit either a horizontal or vertical junction box.
This terminal is normally connected to the reversing valve of the heat pump. It is called O when the valve is energized in cooling and B when it is energized in heating. Option 10 of the Configuration Options makes the O/B selection.
There are several timers which influence the thermostat's operation. If any of the timers listed below is preventing the equipment from turning on, the display icons, which show the equipment is operating, will be flashing to indicate a turn-on delay is present.
The timeguard timer is set to 5 minutes at power up and any time the compressor turns off. The compressor cannot turn on until the timeguard timer has expired.
After a power cycle, a randomized delay will be added to the end of the timeguard timer to prevent multiple units from hitting the power grid all at the same time. The randomization timer is between zero and five minutes. If a demand exists, compressor outputs energize between 5 and 10 minutes after the power cycle.
NOTE: The timeguard can be defeated for one cycle by simultaneously pressing the fan and up keys. The indication of a flashing heat or cool icon means that there is a demand in the space but the equipment is being held off due to the timeguard timer.
Once the equipment has been turned on, it must remain on for 3 minutes. A change in mode or set point will cancel this timer.
The number of equipment cycles per hour is determined by configuration Option 16. Based on the selection of 4, 6 or 8 cycles per hour, this timer is set to 15, 10 or 8 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits. It can be defeated for one cycle by simultaneously pressing the fan and up keys.
The staging timer enforces a minimum number of minutes for the current stage of equipment capacity to be energized before staging up to the next level of capacity. The number of minutes between each stage is configured by the installer in software configuration Option 17.
Three system error messages may appear on the thermostat screen indicating a problem with the thermostat's operation. See below for possible system error messages and their meaning.
If the room temperature sensor fails, the temperature display will show "--" (two dashes). If the space temperature is the average of both the local and remote sensors (as configured in Option 5), and one of the sensors fails, the thermostat will control the valid sensor only. The display will alternate every 10 seconds between "--" for the invalid sensor and the reading from the valid sensor.
The fan setting is specified by Option 36 and cannot be changed by the user. If Option 36 is set to ON, and the fan button is pressed, an E7 error message will be displayed for three seconds and the fan selection will remain ON and not be changed.
If there is an internal memory failure, the temperature display will show "E4" and the thermostat needs to be replaced.
Table 6 can be used as a troubleshooting tool for determining which outputs will be active for a particular configuration and operating mode.
Table 6 — Equipment Outputs
EQUIP CONFIG (Option 01 Setting) | COOL STAGE 1 | COOL STAGE 2 | HEAT STAGE 1 | HEAT STAGE 2 | HEAT STAGE 3 | EM HEAT |
AC | Y1 | Y1, Y2 | W | W, O/B | — | O/B |
HP Option 10=C | Y1, O/B | Y1, Y2, O/B | Y1 | Y1, Y2 | Y1, Y2, W | W |
HP Option 10=H | Y1 | Y1, Y2 | Y1, O/B | Y1, Y2, O/B | Y1, Y2, W, O/B | W |
H | — | — | W | W, O/B | — | O/B |
C | Y1 | Y1, Y2 | — | — | — | — |
WSHP | Y1, O/B | Y1, Y2, O/B | Y1 | Y1, Y2 | Y1, Y2, W | W |
System wiring diagrams are provided for typical Carrier equipment.
See Fig. 7-25.
Fig. 7 — Thermostat Wiring — 42B Motor Controls — Single-Phase Only, 3-Phase Only, Single-Phase with Interlocking Disconnect, and 3-Phase with Interlocking Disconnect
Fig. 8 — Thermostat Wiring — 42B Motor Controls — Single-Phase and 3-Phase with Interlocking Disconnect and Single-Stage Electric Heater
Fig. 9 — Thermostat Wiring — 42B Motor Controls — 3-Phase with Interlocking Disconnect and 2-Stage Electric Heater
Fig. 10 — Thermostat Wiring — 48/50HC, 48/50TC, and 48/50LC04-06 Rooftop Units
Fig. 11 — Thermostat Wiring — 50EJQ, EWQ024, 028 Heat Pump Units
Fig. 12 — Thermostat Wiring — 50HJQ004-016 Units
Fig. 13 — Thermostat Wiring — 50HQL, KQE, KQL, P1, PC, PEC, PS, PSW, PT, RHC, RHE, RHR, RHS, RTG, RVC, RVE, RVR, RVS, RWS, VQL Water Source Heat Pump Units with Complete C Controls and Duct Heating Option
Fig. 14 — Thermostat Wiring — 50HQL, KQE, KQL, P1, PC, PEC, PS, PSW, PT, RHC, RHE, RHR, RHS, RTG, RVC, RVE, RVR, RVS, RWS, VQL Water Source Heat Pump Units with Deluxe D Controls
Fig. 15 — Thermostat Wiring — 50HQL, KQE, KQL, P1, PC, PEC, PS, PSW, PT, RHC, RHE, RHR, RHS, RTG, RVC, RVE, RVR, RVS, RWS,VQL Water Source Heat Pump Units with Complete C Controls
Fig. 16 — Thermostat Wiring — 50VS Water Source Heat Pump Units
*Connection not required.
†W2 connection not required on units without electric heating.
Fig. 17 — Thermostat Wiring — 50HCQ,TCQ Rooftop Units
*Connection not required.
Fig. 18 — Thermostat Wiring — 50HJQ014,016 Heat Pump Units
*Connection not required.
Fig. 19 — Thermostat Wiring — 38ARD Commerical Split System Units
Fig. 20 — Thermostat Wiring — 38ARQ008-012 Series and 40RMQ008-012 Series Split System Units
Fig. 21 — Thermostat Wiring — 38AU Commercial Split System Units with 40RUA Air Handler Units
Fig. 22 — Thermostat Wiring — 40RU/38RU Packaged Air-Handler Units
NOTE:
Selection: rS, SA, Od, rA
rS — remote space temperature
SA* — sensor supply air temperature
Od* — sensor outdoor air temperature
rA* — sensor return air temperature
*Display only, not used for temperature control
Fig. 23 — Thermostat Wiring — Outdoor Air Temperature and Remote Room Temperature Sensors
Fig. 24 — Thermostat Wiring — Space Temperature Sensor Averaging Wiring (4 Sensor Application)
Fig. 25 — Thermostat Wiring — Space Temperature Sensor Averaging Wiring (9 Sensor Application)
Read entire instruction before installing the thermostat.
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert symbol .
When the safety alert symbol is present on equipment or in the instruction manual, be alert to the potential for personal injury.
Understand the signal words
,
, and
.
These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death.
WARNING signifies a hazard which could result in personal injury or death.
CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the Comfort Pro and is the answer not in the manual?
Questions and answers