Advertisement
GoodWe ES series inverters (hybrid) are bidirectional which apply to PV system with battery to store energy.
Energy produced by the PV system is used to optimize self-consumption; excess energy is used to charge the batteries, and then fed into the public grid when the PV energy is adequate,
When PV energy output is insufficient to support connected loads, the system automatically get energy from the batteries if battery capacity is abundant. If the battery capacity is insufficient to meet own consumption requirements, electricity will be drawn from the public grid.
GoodWe ES series inverter is design for both indoor and outdoor use.
See fig. 1-1 for example of Basic hybrid PV system
Before using the inverter, please read all instructions and cautionary markings on the unit and this manual. Store the manual where it can be accessed easily.
The ES series inverter of Jiangsu GoodWe Power Supply Technology Co. Ltd. (hereinafter referred to as GoodWe) strictly conforms to related safety rules in design and test.
Improper operation may have a risk of electric shock or damage to equipment and property.
Caution! Failure to observe a warning indicated in this manual may result in injury. | ![]() | The package/product should be handled carefully and never be tipped over or slung. | |
Danger of high voltage and electric shock! | ![]() | This side up; the package must always be transported, handled and stored in such a way that the arrows always point upwards. | |
Danger of hot surface! | ![]() | No more than six (6) identical packages may be stacked on each other. | |
![]() | Signals danger due to electrical shock and indicates the time (5 minutes) to allow after the inverter has been turned off and disconnected to ensure safety in any installation operation. | ![]() | Keep dry; the package/product must be protected from excessive humidity and must be stored under cover. |
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
Mounting location should be selected based on the following aspects:
Remember that this inverter is heavy! Please be carefully when lifting out from the package.
Before connecting to Grid and Load, please install a separate AC breaker (250VAC/30A) between inverter and Grid. This will ensure the inverter can be securely disconnected during maintenance.
It's very important for system safety and efficient operation to use appropriate cable for AC connection. To reduce risk of injury, please use the proper recommended cable size. Refer to Figure 4.1-1.
Grade | Descriptio | Value |
A | O.D. | 10~12mm |
B | Conductor Material Sectional Area | 3~4mm2 |
C | Bare Wire Length | 10mm around |
Please follow below steps to implement AC connection:
There are two types of DC plugs, SUNCLIX and MC4 series. Please refer to Figure 4.2-1.
Installation instruction of SUNCLIX please refer to Figure 4.2-2.
Installation instruction of MC4 please refer to Figure 4.2-3.
Before connecting to battery, please install a separate DC breaker (60A for GW3648D-ES and 120A for GW5048D-ES) between inverter and battery. This will ensure the inverter can be securely disconnected during maintenance.
Grade | Description | Value |
A | O.D. | 10~12mm |
B | Conductor Material Sectional Area | 20~25mm2 |
C | Bare Wire Length | 10mm around |
Please follow below steps to implement battery connection:
RS485 interfaces are used for EzConverter and EzMeter communication. The cable length should not exceed 800m. For the connection methods of RS485 please refer to the next two chapters.
Please follow below steps to implement RS485 connection of inverter side:
EzMeter can detect the current magnitude and direction, to control the working condition of inverter. Inverter and EzMeter communication via RS485, The cable length should not exceed 800m.
For the connection method of single phase EzMeter refer to Figure 4.5-1.
For the connection method of three phases EzMeter refer to Figure 4.5-2.
(optional)
It is needed to configure EzConverter if lithium battery is used in the system, to communicate with battery BMS.
Inverter and EzConverter communication via RS485, lithium battery and EzConverter communication via RS485 or CAN or RS232 (depend on Li-Ion battery communication type).The cable length should not exceed 2m.
Choose corresponding dial-up circuit of lithium battery, according to dial-up protocol comparison table of lithium battery from user manual.
EzConverter work status as below table 4.6-1.
TABLE 4.6-1 | |||
Silk-Screen | LED Color | EzCoverter Status Note | LED Display Status |
Power | Green | Powered on | Constant on |
Inverter | Yellow | Communicate with Inverter | Blink |
RS485 | Yellow | Communication OK | Blink |
CAN | Yellow | Communication OK | Blink |
RCR | Yellow | Received command from RCR | Blink |
RS232 | Yellow | Communication OK | Blink |
Install the antenna to inverter. Refer to Figure 4.7-1.
WiFi reload function is used to change the WiFi configuration to default value. Please reconfigure the WiFi as per WiFi configure illustration after using the function.
The USB communication is used for firmware update only!
Please follow below Figure 4.9-1 to implement USB connection
Inverter Status | LED Color | Inverter Status Note | LED Display Status |
WiFi | Yellow | WiFi Reset or Reload OK | Blink 0.2s on 0.2s off |
WiFi Router NG | Blink 0.5s on 0.5s off | ||
WiFi Server NG | Blink 2.5s on 2.5s off | ||
WiFi Server OK | Constant on | ||
Normal | Green | Normal | Constant on |
Checking | Blink 0.5s on 0.5s off | ||
Fault | Red | Fault | Constant on |
Grid Fault | Blink 2s on 2s off | ||
Sale | Blue | Generate to grid | Constant on |
Feeding to Grid is Off | Blink 2s on 2s off | ||
Buy | Blue | Consumption from grid | Constant on |
Charge | Blue | Battery Charging | Constant on |
Discharge | Blue | Battery Discharging | Constant on |
Bat Low | Red | Battery Low / Bad / Disconnect | Blink 1s on 1soff |
ES Series inverter has no LCD screen, it can be controlled via mobile device with the APP software (EzManage).
Besides, through scan the QR code to be installed too.
Google play
Android market
If this is your first time to install GoodWe Hybrid Inverter, please first connect the battery and solar panels to the inverter and keep the inverter off-grid, then you can set the inverter in "Setting" menu through Ezmanage with the following steps. After finishing the setting, connect to grid, Then the inverter starts to work.
![]() | Plan 1.Connect the inverter directly! Please choose the SSID of inverter (Solar-WiFi as default, initial password: 12345678) and join it. |
Plan 2.Connect through wireless router! If inverter has joined local WiFi network, you can choose the SSID of WiFi router and join it. |
If you have any questions, please refer to WiFi Connection Guide.
![]() |
Attention: |
![]() | Click to synchronize time setting with your monitoring device |
![]() | Battery Setting |
![]() |
|
|
![]() | Battery Setting |
![]() | Grid Charge Time: During this time period, gird will charge battery automatically. |
Grid Charge Power: Set grid charge power limits(0-50%). | |
Battery Discharge Time: During this time period, the battery will discharge. | |
Battery Discharge Power: Set battery discharge power limits(0-100%). | |
Attention: If there is overlap between charge time and discharge time, charge is preferred. |
![]() | Advanced Settings |
![]() | Feeding To Grid: When the switch is "yes", excess energy of PV can feed to grid. |
Shadow Scan: When switch is "on", it can resolve the multiple wave problems of PV pannels. | |
PV Charge Without Grid: When switch is "on", PV can charge battery without grid. This | |
Function can be set in off-grid and must have PV. | |
Back-up Function: When switch is "on", it allows the Back-up port to output. | |
Start Back-up Output: When grid is unreachable, we can start Back-up manually. |
![]() | |
![]() | Solar Yield
|
![]() | Check the battery level
|
![]() |
ES series inverters have the following main work modes based on different conditions:
Mode1: Energy produced by the PV system is preferred for local load. And the excess energy is first used for charging batteries, then feeding to the grid. | ![]() | |
Mode2: If there is no PV, battery energy is used for local load first, the grid also can supply when the battery capacity is not enough. | ![]() | |
Mode3: If the grid is fault or there is no grid, the system can still work, PV and batteries supply energy for local load. | ![]() | |
Mode4: The battery can be charged by the grid, time and power of battery charging can be set up flexibly. | ![]() |
An error message will be displayed on the APP if a fault occurs.
Table 8-1 is the Description of Error Message
Error message | Description |
Utility Loss | Grid disconnected |
Fac Failure | Grid frequency no longer within permissible range |
PV Over Voltage | Overvoltage at DC input |
Over Temperature | Overtemperature on the case |
Isolation Failure | Ground insulation impedance is too low |
Ground I Failure | Overhigh ground leakage current |
Relay-Check Failure | Relay self-checking failure |
DC Injection High | Overhigh DC injection |
EEPROM R/W Failure | Memory chip failure |
SPI Failure | Internal communication failure |
DC Bus High | Overhigh BUS voltage |
AC HCT Failure | Output current sensor failure |
GFCI Failure | Detection circuit of ground leakage current failure |
Vac Failure | Grid voltage no longer within permissible range |
Battery Over Temperature | Battery Over Temperature |
Battery Under Temperature | Battery Under Temperature |
Battery Cell Voltage Differences | Li-Ion Battery Cell Voltage Differences |
Battery Over Total Voltage | Li-Ion Battery Over Total Voltage |
Battery Discharge Over Current | Battery Discharge Over Current |
Battery Charge Over Current | Battery Charge Over Current |
Battery Under SOC | Battery Capacity Low |
Battery Under Total Voltage | Battery Under Total Voltage |
Battery Communication Fail | Battery Communication Fail |
Battery Output Short | Battery Output Short |
Table 8-1
Model | GW5048D-ES | GW3648D-ES |
Solar | ||
* Max. DC power(W) | 5400 | 4200 |
Max. DC voltage (V) | 580 | 580 |
MPPT voltage range (V) | 125~550 | 125~550 |
Starting voltage (V) | 125 | 125 |
Max. DC current (A) | 15/15 | 15/15 |
DC overcurrent protection(A) | 20 | 20 |
No. of DC connectors | 2 | 2 |
No. of MPPTs | 2(can parallel) | 2(can parallel) |
DC overvoltage category | Category Ⅱ | |
DC connector | SUNCLIX / MC4 (Optional) | |
Battery | ||
Battery Type | Lead-acid or Li-Ion | Lead-acid or Li-Ion |
Battery Rated voltage (V) | 48 | 48 |
MAX Discharge power (W) | 4600 | 4600 |
Charge current (A) | 5-50 A continuous, programmable | 5-50 A continuous, programmable |
Battery capacity (Ah) | >100AH(depending requirement) | >100AH(depending requirement) |
Charging curve | 3-stage adaptive with maintenance | 3-stage adaptive with maintenance |
Charging voltage | 57V | 57V |
Battery temperature compensation | included(Li-Ion) | included(Li-Ion) |
Battery voltage sense | integrated | integrated |
Current shunt | integrated | integrated |
AC Output Data | ||
Norminal AC power(W) | 4600 | 3600 |
Max. AC power(W) | 4600 | 3600 |
Peak power (Back-up)(W) | 1.5x Pnom, 10sec | 1.5x Pnom, 10sec |
Max. AC current(A) | 20 | 16 |
AC overcurrent protection(A) | 30 | 24 |
Norminal AC output | 50/60Hz; 230Vac | |
AC output range | 45~55Hz/55~65Hz; 180~270Vac | |
AC output (Back-up) | 230Vac ±2%, 50Hz ±0.2%, THDv<3%(linear load) | |
THDi | <1.5% | |
Power factor | 0.9 leading~0.9 lagging | |
Grid connection | Single phase | |
AC overvoltage category | Category Ⅲ | |
Efficiency | ||
Max. efficiency | 97.6% | 97.6% |
Euro efficiency | 97.0% | 97.0% |
MPPT adaptation efficiency | 99.9% | |
Protection | ||
Residual current monitoring unit | Integrated | |
Anti-islanding protection | Integrated | |
DC switch(PV) | Integrated (optional) | |
AC over current protection | Integrated | |
Insulation monitoring | Integrated | |
Certifications&Standards | ||
Grid regulation | VDE4105, VDE 0126-1-1+A1, G83/2, G59/2, AS4777.2/.3, IEC62109-2 | |
Safety | IEC62109-1&-2, AS3100, IEC62040-1 | |
EMC | EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4, EN61000-3-11, EN61000-3-12 | |
General Data | ||
Dimensions (WxHxD) | 516*440*184mm | 516*440*184mm |
Weight (kg) | 30 | 28 |
Mounting | Wall-mounted Bracket | |
Ambient temperature range | -25~60°C (>45°C derating) | |
Relative humidity | 0~95% | |
Moisture location category | 4K4H | |
Max. operating altitude | 2000m | |
Protection degree | IP65 | |
Environment category | Outdoor & indoor | |
External environment pollution degree | Grade1, 2, 3 | |
Topology | Transformerless | |
Standby losses(W) | <8 | |
Cooling | Nature convection | |
Noise emision(dB) | <25 | |
Display | LED light & APP | |
Communication | USB2.0 or WiFi | |
Standard warranty(years) | 5/10/15/20/25 (optional) |
* It is recommended that the total peak power of PV strings should not exceed 130% of maximum DC power of inverter listed in the table.
Note
Overvoltage category definition
Category I: applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a low level.
Category II: applies to equipment not permanently connected to the installation. Examples are appliances, portable tools and other plug-connected equipment;
Category III: applies to fixed equipment downstream of and including, the main distribution board. Examples are switchgear and other equipment in an industrial installation;
Category IV: applies to equipment permanently connected at the origin of an installation (upstream of the main distribution board). Example are electricity meters, primary overcurrent protection equipment and other equipment connected directly to outdoor open lines.
Moisture location category definition | |||
Moisture parameters | Level | ||
3K3 | 4K2 | 4K4H | |
Temperature Range | 0~+40℃ | -33~+40℃ | -20~ +55°C |
Humidity Range | 5%~85% | 15%~100% | 4%~100% |
Environment category definition
Outdoor: the ambient air temperature is -20~50°C, Relative humidity range is 4% to 100%, applied to PD3
Indoor unconditioned: the ambient air temperature is -20~50°C, Relative humidity range is 5% to 95%,applied to PD3
Indoor conditioned: the ambient air temperature is 0~40°C, Relative humidity range is 5% to 85%,applied to PD2
Pollution degree definition
Pollution degree 1: No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or, dry, non-conductive pollution occurs which becomes conductive due to condensation which is expected.
Pollution degree 4: Persistent conductive pollution occurs, for example, the pollution cause by conductive dust, rain and snow.
Global Service Hotline: +86 4009-281-333
GoodWe(China)
No.189 Kunlunshan Rd., SND,
Suzhou, 215163, China
T: +86 512 6239 6771
service@goodwe.com.cn
www.goodwe.com.cn
GoodWe(Europe)
Mürwikerstr. 59
24943 Flensburg Germany
T: +49 461 5897 0235
europe@goodwe.com.cn
www.goodwe.de
GoodWe(Australia)
74 Tarana Avenue,
Glenroy VIC 3046, Australia
T: +61 3 9972 9938
australia@goodwe.com.cn
www.goodwe.de
GoodWe(Netherlands)
Zevenwouden 194,
3524 CX Utrecht, the Netherlands
T: +31 6 1988 6498 +31 6 1784 0429
service@goodwe.com.cn
www.goodwe.com.cn
GoodWe(UK)
93 Caversham Place
Sutton Coldfield B73 6HW
T:+44 12 1238 0053
uk@goodwe.com.cn
www.goodwe.com.cn
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the ES Series and is the answer not in the manual?
Questions and answers