ComAp InteliLite NT AMF26-P Reference Manual
ComAp InteliLite NT AMF26-P Reference Manual

ComAp InteliLite NT AMF26-P Reference Manual

Compact controller for stand-by operating gen-sets

Advertisement

Quick Links

NT
InteliLite
InteliLite NT AMF26-P
Compact Controller for Stand-by Operating Gen-sets
(IL-NT AMF26-P unit)
SW version 2.4 January 2016
Modular Gen-set Controller
Copyright © 2015 ComAp a.s.
Written by Petr Novák
Customized by Michal Novak
Prague, Czech Republic
ComAp, a.s.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 2 66316661, Fax: +420 2 66316647
E-mail: info@comap.cz, www.comap.cz
Reference Guide

Advertisement

loading
Need help?

Need help?

Do you have a question about the InteliLite NT AMF26-P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ComAp InteliLite NT AMF26-P

  • Page 1 Compact Controller for Stand-by Operating Gen-sets (IL-NT AMF26-P unit) SW version 2.4 January 2016 Reference Guide Modular Gen-set Controller Copyright © 2015 ComAp a.s. ComAp, a.s. Written by Petr Novák Kundratka 2359/17, 180 00 Praha 8, Czech Republic Customized by Michal Novak...
  • Page 2: Table Of Contents

    Inputs and Outputs ..........................48 Binary inputs IL-NT - default ......................48 Binary inputs - list ..........................48 Binary outputs IL-NT - default ......................53 Binary outputs - list ..........................53 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 3 Alarms ............................. 129 Browsing ECU Alarms ........................129 Earth Fault Protection Test ......................129 Setpoint Change ..........................131 Entering the Password ........................131 Controller Information Screen ......................132 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 4 IL-NT S-USB interface (optional card) .................... 165 IL-NT-AOUT8 interface (optional card) ................... 165 IL-NT-EFCPM interface (optional card) ..................165 IL-NT-EFCPM2 interface (optional card) ..................165 IGS-PTM ............................166 IGL-RA15 ............................166 IG-IB ..............................167 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 5: General Guidelines

    This manual describes „AMF26-P“ software, which is designed for single set, stand-by applications. What is the purpose of the manual? Manual also provides general information how to install and operate InteliLite NT AMF26-P controller. This manual is dedicated for Operators of gen-sets...
  • Page 6: Dangerous Voltage

    (Yellow background) new features and text changed from version 1.0 Note: ComAp believes that all information provided herein is correct and reliable and reserves the right to update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.
  • Page 7: General Description

    *** Supported from version IL-NT AMF 26-P- 2.2 Hint: For detailed information about extension modules used with IL-NT controllers, please see the IL-NT- Accessory Modules manual. IL-NT RS232 Communication module InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 8 The following procedure is analogic also for other communication modules. 1. Insert a screwdriver into the slot of the cover. 2. Move the screwdriver to set apart the small cover. Be careful! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 9 3. Remove the small cover. 4. Break apart the small cover into two pieces. Do not throw away the smaller part! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 10 5. Take RS 232 communication module. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 11 When you insert RS 232 communication module, the boot jumper is hidden. For that reason we recommend to use RS 232 communication module with the boot jumper placed on it. See pictures below: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 12: Il-Nt Rs232-485 Communication Module

    It is supposed to be installed permanently. Should you need to remove it, the safest way is to remove whole back cover and than remove module manually. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 13: Il-Nt S-Usb Service Usb Communication Module

    It is supposed to be used as a service tool. When you need to remove it, grab module in cutouts and pull it up manually. Hint: Use the shielded USB A-B cable with this module! Recommended is ComAp cable – Order code: “ ”.
  • Page 14: Ib-Lite Ethernet Communication Plug-In Card

    COM1 Mode = DIRECT COM2 Mode = MODBUS. Hint: The module requires some settings before initial usage. See for more IB-Lite-1.2-Reference Guide.pdf details about IB-Lite communication plug-in card. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 15: Internetbridge Nt

    This module incorporates support of AirGate technology for plug and play connection via GPRS. Module is usually used for connection to remote monitoring and controlling systém. WebSupervisor (http://websupervisor.comap.cz) or to LiteEdit PC software. Module is capable of sending alarm SMS based on settings in SMS/Email setpoint group.
  • Page 16 AOUT8 fits to “extension module” slot and after installing IL-NT-AOUT8 you do not put back the small cover. PC Installation Suite consist a set of prepared converting curves for basic usage of PWM outputs with automotive gauges. IL-NT-AOUT8 module: Typical wiring: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 17: Il-Nt Rd Remote Display Software

    RS232-485 communication module or when RS232/RS485 converters are used. The IL-NT RD hardware type should fit to the master IL-NT. Hint: Please see the “IL-NT-RD Remote display software” chapter for more details. IL-NT-EFCPM InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 18: Il-Nt-Efcpm2

    The remote announciator IGL-RA15 can be connected to the IL-NT unit via CAN bus. Any of the binary outputs can be configured (using LiteEdit software) to each LED diode on the RA15. The module can be also enabled or disabled using LiteEdit software. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 19: Ig-Iom/Ptm Module

    - For a description of setting IGS-PTM module with current/voltage sensors please see the Extension modules manual. - When module is not configured by LiteEdit SW, controller does not show related values and InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 20: Ig-Ib Internet Bridge

    See the documentation of IGS-PTM for the technical and function description. IG-IB Internet bridge IG-IB Internet bridge enables InteliLite for Ethernet/Internet communicatons. It is connected to controller via RS232 line. See InteliCommunication Guide for further details. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 21 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 22: Il-Nt Terminals And Front Fascia

    IL-NT Terminals and front fascia IL-NT terminals and front fascia InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 23: Installation

    The controller is to be mounted onto the switchboard door. Requested cut out size is 175x115mm. Use the screw holders delivered with the controller to fix the controller into the door as described on pictures below. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 24: Recommended Wiring

    Hint: MCB and GCB is recommended to be mechanically interlocked. It is possible to start Volvo and Scania engines via CAN bus. See Engines started via CAN bus. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 25: Stand-By Applications

    Stand-by Applications Contactors (set point MCB Logic = “CLOSE-OFF”) LOAD +24V(12V) ATS with two stable positions (set point MCB Logic = “CLOSE-ON”) LOAD +24V(12V) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 26: Ats With Three Stable Positions (Set Point Mcb Logic = "Close-Off")

    Detailed description: There is a basic communication interface between Master and Slave controller realized by interconnection of two wires (DualAMFCtrlIn, DualAMFCtrlOut) on both. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 27 [1..24], step = 1 hour. Default setting is 6 hours. This timer is reset when load is transferred back to healthy mains Example of setting the Dual AMF function: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 28 10- System is now ready for DualAMF function. Wiring of system with selectable MASTER and SLAVE role settings: Hint: GCB and MCB breakers feedbacks are recommended, but not required. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 29: Getting Started

    Switchboard and engine has to be grounded in common spot. Use as short as possible cable to the grounding point. Power supply To ensure proper function: Use min. power supply cable of 1,5mm InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 30 Voltage before dip is 12V, after 150ms the voltage recovers to min. allowed voltage, i.e. 8V Hint: Before the battery is discharged the message "Low BackupBatt" appears. Or by connecting special I-LBA Low Battery Adaptor module: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 31: Power Supply Fusing

    Binary output protections Hint Do not connect binary outputs directly to DC relays without protection diodes, even if they are not connected directly to controller outputs. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 32: Magnetic Pick-Up

    Speed Control Unit ESD 5500 Power Supply Power Supply Battery Be aware of interference signal from Speed governor when one speed pick-up is used. If engine will not start: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 33: Current Measurement

    Check ground connection from pick-up to controllers, eventually disconnect ground connection to one of them Galvanically separate IL-NT RPM input using ComAp separation transformer RPM-ISO (1:1) Use separate pick-up for Speed governor and InteliLite Hint: In some cases the controller will measure a RPM value even though the gen-set is not running: RPM is measured from the generator voltage (Gear Teeth = 0) IL-NT is measuring some voltage value on input terminals due to open fusing.
  • Page 34: Earth Fault Measurement (Module)

    TRIP output are activated. Earth Fault protection is not active when MCB is closed and also when EF Protection: DISABLED. For manual protection simulation can be used function. EF Prot Test Earth Fault Protection Test InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 35 The wiring should be accordant with that. IL-NT-EFCPM Input Description Input range up to 8,32 mA (earth fault protection input) Common (earth fault protection input) Binary input 1 – EMERGENCY STOP* InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 36: Voltage Measurement And Generator Connection Types

    There are 4 voltage measurement ConnectionType options, every type matches to corresponding generator connection type. ConnectionType: 3 Phase 4 Wires Three phase “wye” measurement – 3PY 3 Phase 4 Wires - STAR Connecti InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 37 Only L1, L2 and L3 wires should be connected. In case of EDISON DELTA connection the N (neutral) wire (in the diagram connected between T6 and T9) has to be disconnected. No separation transformers for three wires voltage connection (without N) are needed. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 38 Single-phase measurement – 1PH Split Phase – DOUBLE DELTA Connection – ZIG ZAG (DOG LEG) Connection ConnectionType: Mono Phase Single-phase measurement – 1PH Mono Phase – MONOPHASE Connection InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 39 Hint: Switchboard lighting strike protection according standard regulation is expected for all 4 connection types!!! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 40: Analog Inputs

    (Valid only for analog inputs) Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and delay adjust in Extension I/O and Engine Protect group. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 41 Mixed connection of IL-NT analog inputs: AI1 – binary input AI2 – three state input AI3 – analog resistive input Wiring Wiring diagrams of analog inputs WIRING OF ANALOG INPUTS-GROUNDED SENSORS InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 42 “Not used” – analog input isn’t used ”Alarm” – analog input is used Set to: Alarm Name: Name of the analog input. Maximally 14 letters. Set to: Water Temp InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 43 Each Analog input has separate triplet of setpoints: Wrn level, Sd level, AI del. Names of these setpoints are fix defined Number of decimal points of Wrn level and Sd level is the same as the configured number of decimal points of measured value. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 44: Recommended Can/Rs485 Connection

    A) For shorter distances (all network components within one room) – picture 1 Interconnect H and L; shielding connect to PE on controller side B) For longer distances (connection between rooms within one building) – picture 2 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 45 C) In case of surge hazard: 3106A Paired - EIA Industrial RS-485 PLTC/CM (1x2+1 conductors) Picture 1 - shorter distances (all network components within one room) 120 Ω 120 Ω InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 46: Extension Modules (Can Bus) Connection

    PT5-HF-5DC-ST (RS485) Extension modules (CAN bus) connection CAN H CAN H CAN L CAN L IL-NT 10 ohm 15nF EXTENSION IGL-RA15 (optional) IGS-PTM (optional) MODULES 120 ohm IG-IOM (optional) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 47: Connection Rules

    IL- NT – IGS-PTM – IGL-RA15 It is possible to connect only one IG-IOM or IGS-PTM and one IGL-RA15 to IL-NT. button in LiteEdit configuration window to activate CAN (J1939) interface. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 48: Inputs And Outputs

    Warning Shut down Alarm active All the time Valid if checkbox “Engine running only” is not checked Engine running only Valid if checkbox “Engine running only” is checked InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 49: Emergency Stop

    If the input is closed, no setpoints can be adjusted from controller front panel and gen-set mode (OFF- MAN-AUT-TEST) cannot be changed. Hint: Access Lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified changes the selected setpoints can be password protected. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 50: Remote Off

    The controller shows “EmergMan” state and the engine can not be started. Generator current and power measurement is active in this mode, regardless of the actual state of the engine. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 51: Start Button

    To secure proper functionality of this function Engine Params: Prestart Time has to be set for at least 1 second (Prestart Time >= 1) otherwise there might be not enough time to block the start sequence. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 52 Nominal RPM B = Nominal RPM A * 60 / Nominal Freq A When the input is active it is not possible to change Nominal Freq and Nominal RPM parameters values, neither from LiteEdit nor from controller display. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 53: Binary Outputs Il-Nt - Default

    Battery A and closes for the second cranking cycle which is designated for Battery B (in case that 2 batteries for cranking are used). InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 54: Fuel Solenoid

    The output IDLE/NOMINAL closes after the timer Idle Time elapses. The Idle Time counter starts to countdown when Starting RPM reached. The Underspeed protection is not evaluated during fixed 5 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 55 The output controls the generator circuit breaker. Hint: Supposed time to close (reaction time) of GCB is 0,1 sec. GCB ON Coil The output activates Generator Circuit Breaker coil. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 56 The output closes if the engine is in Running state. Cooling The output closes when gen-set is in Cooling state. Supplying Load Closed when the generator current is > 0,5% of the CT ratio. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 57: Glow Plugs

    Basic settings setpoint group. When Fuel level value (measured on Analog Input 3) drops below/on level given by Engine Params: Fuel Pump ON, then binary output FUEL PUMP is activated. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 58: Dummy Load

    When L1 Amps >= DummyLd 2 OFF and Dummy Load function is active then Dummy Load 2 = 0 The outputs are activated/deactivated according to Dummy Ld 1..2 ON/ Dummy Ld 1..2 OFF parameters and also according to Dummy Load parameter which determines when the function/output InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 59 FAULT RESET is pressed AL Gen <V The output closes if the generator undervoltage shutdown alarm activates. The output opens, if: alarm is not active and FAULT RESET is pressed InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 60 AL Gen Volts The output closes if the generator over/under voltage alarm or voltage asymmetry alarm activates. The output opens, if: alarm is not active and FAULT RESET is pressed InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 61 This protection goes active 60s after stop command. With start goes this protection inactive. The output opens, if: alarm is not active and FAULT RESET is pressed InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 62 FAULT RESET is pressed AL MainsCCWRot The output closes when wrong mains phase sequence is detected. The output opens, if: No warning alarm is active and FAULT RESET is pressed InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 63 The output closes if the engine temperature (configured to the second analog input) warning alarm activates. The output opens, if: alarm is not active and FAULT RESET is pressed InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 64 This output can be used to indicate when the ECU should be powered up i.e. only while the engine is running. This output also influences evaluation of communication failure with ECU and related FLS alarms from InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 65: Remote Connect

    This output copies state of “R” letter which is visible on controlle display in case any Remote connection is active. When “R” is visible the output is active, when not visible the output is not active. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 66: Analog Inputs

    Optional plug in card IL-NT AOU8 provides eigth Pulse-With-Modulation (PWM) outputs. These are intended to drive VDO style analog gauges. This is to provide visual indication of typically ECU values InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 67 PWM signal emulates sensor which would be typically mounted on the engine. Any value from controler may be configured to the outputs. Use LiteEdit PC SW to configure coresponding sensor/gauge curve and value selection. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 68: Setpoints

    WARNING! When you change the firmware, statistics can be invalid! WARNING! Change of CT ratio over value 250 without reconfiguring in LiteEdit can cause overflow of current measurement and improper function of controller! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 69 1 – 2000 A / 1A PT Ratio [/1] Gen-set potential transformers ratio. Step: 0,1 V / V Range: 0,1 – 500,0 V / V Vm PT Ratio [/1] Mains potential transformers ratio. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 70 [3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph] 3Ph4Wire: STAR Connection, 3 phases and neutral - 4 wires, Three phase “wye” measurement – 3PY 3Ph3Wire: DELTA Connection, 3 Phase without neutral - 3 Wires, InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 71: Comms Settings

    DIRECT: LiteEdit communication protocol via direct cable. MODEM: LiteEdit communication protocol via modem. MODBUS: Modbus protocol. See detailed description in InteliCommunication guide. ECU LINK: Protocol for communication with Cummins engines via Modbus. Hint: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 72 If DHCP is ENABLED this setpoint is used to display the gateway IP address which has been assigned by the DHCP server. A gateway is a device which connects the respective segment with the other segments and/or Internet. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 73 ComAp PC program (i.e. InteliLIte, InteliMonitor). This setpoint should be adjusted to 23, which is the default port used by all ComAp PC programs. A different value should be used only in special situations as e.g. sharing one public IP address among many controllers or to overcome a firewall restrictions.
  • Page 74: Engine Params

    1% of nominal RPM Range: 5 – 50 % Starting Oil P [Bar] When reached controller stops cranking (starter goes OFF). Step: 0,1 bar Range: 0,0 – 10,0 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 75 Underspeed possibly caused by instability of the engine short after start. Min Stab Time Minimum time after reaching of defined level of RPM to the closing GCB. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 76: Cooling Time

    MAN mode when the gen-set is stopped and STOP button is pressed (..and in the same cases as Fuel Solenoid: DIESEL) - the output opens InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 77 3. Change the setpoint ECU FreqSelect and confirm it by pressing Enter 4. Press the Stop button on the IL controller. The whole procedure (step 2 to 4) must not exceed 10 seconds. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 78 Input to the comparator, it is possible to choose what analog input will be evaluated Comparator ON Resolution = 1 ON limit - once this limit is reached the Comparator output is switched on. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 79 Dummy Load parameter conditions are fulfilled (GCB and/or MCB closing and switching to Ready To Load state). Once the function is activated (after 15 seconds delay) Dummy Load ON/OFF limits are evaluated immediately without any delay. Hint: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 80: Engine Protect

    Horn timeout has elapsed. Step: Range: 0 – 600 s Overspeed Threshold for over speed protection InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 81 AI3 Sd Shutdown threshold level for ANALOG INPUT 3 Step: Range: -100 – 10000 AI3 Del Delay for ANALOG INPUT 3 Step: Range: 0 – 900 s Hint: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 82: Gener Protect

    Threshold for generator overload (in % of Nominal power) Step: 1% of Nominal power Range: 0 – 200% Overload Del Delay for generator overload alarm. Step: 0,1s Range: 0 – 600,0 s InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 83 IDMT Curr No action 20 s 0,2 s No action 200 s 20 s Reaction time No action No action 200 s 20 s (time > 900 s) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 84 For more information about Earth Fault Protection see Earth Fault measurement. Earth Fault Del [s ] Delay for Earth Fault Sd evaluation Step: 0,01 Range: 0,03 to 5,00 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 85 0,0 – 200 (Gen >Freq Sd ) % of Nominal frequency Gen Freq Del Delay for generator underfrequency and overfrequency alarm. Step: 0,1s Range: 0,0 – 600,0 s InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 86: Amf Settings

    1 – 3600 s MFB MReturnDel Delay after the mains return to the GCB opening in case BI: MainsFailBlock is active . Step: Range: 1 – 3600 s InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 87 Delay after MCB opening to GCB closing if the setpoint MCB Opens On set to GENRUN Step: 0,1s Range: 0 – 600,0 s The time charts bellow show recommended setting of AMF Settings:Transfer Del setpoint. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 88 Step: 1% of nominal voltage Range: 50% – 150 (Mains >V)% Mains V Del Delay for mains undervoltage and overvoltage Step: 0,1 s Range: 0 – 600,0 s InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 89 When the output MCB CLOSE/OPEN is closed – MCB should be opened. iL “OFF” iL “ON ” Mains O.K. Mains O.K. MCB logic = ”CLOSE-ON” Mains Failure Signal after external MCB logic = ”CLOSE-OFF” inverted relay InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 90 EmergStart Del), reaches Running state, reaches proper voltage and frequency and Min Stab Time elapses. After that, the MCB is opened, Transfer Del timer is started and the GCB is closed after the timer elapses. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 91: Date/Time

    Defines time of TIMER 1..3 activation. NONE: Timer function is disabled MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY: Timer is activated on daily basis. MON-FRI, MON-SAT, SAT-SUN, SUN-MON: InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 92: Sensors Spec

    The shutdown level for IOM ANALOG INPUT 1..4 alarm detection. Step: Range: -100 – +10000 IOM AI1..4 Del Delay for IOM ANALOG INPUT 1..4 alarm. Step: Range: 0 – 900 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 93: Sms/E-Mail

    Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs. Hint The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s) TelNo/Addr Ch1-4 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 94 “####” as in LiteEdit or on controller display, but by value -32768. In case the message is not send following alarm and history record appears SmsRprtCH1Fail or SmsRprtCH2Fail. Step: Range: 0 – 1000 h InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 95 #<Gen-set name>: <Fuel level>,<Run Hours>,<Engine Temp>,<Bat voltage>,<Oil Pressure>,<Engine state>,<Breaker state>,<Gen V L1-N>,<Gen V L2-N>,<Gen V L3-N>,<Gen Freq>,<Gen PF>,<Mains V L1-N>,<Mains V L2-N>,<Mains V L3-N>,<Mains freq> For more details about this function see SMS Message Control. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 96: Man Operations

    Maintenance setpoint shouldn’t be obviously changed at all and even if it should be judged seriously and changed separately and not as a part of restore to default command. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 97: Alternate Cfg

    Alternate Cfg chosen group or in Basic Settings the setpoints’ values are automatically changed in both groups simultaneously (till new gen-set start request when new evaluation is started). InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 98: Service Timers

    It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than the maintenance function is disabled and counter does not count. Alarm can be acknowledged from InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 99 . Alarm can be acknowledged from controller front face panel or using Direct connection between controller and LiteEdit by double pressing Fault Reset. Step: Range: 0 –9999day InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 100 Hint: Alarm list can display only 16 alarms, if all Service timers are flagging at the same time some of them won‘t be display in the alarm list. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 101: Ecu-Controlled Engine Support

    RA15). Pressing the ECU button in Configuration window of LiteEdit opens ECU dialog window where the appropriate engine/ECU type should be selected. The actual list of ECU types is available on ComAp website in "ECU list - x.y.iwe" package. Download this package and import it into LiteEdit in the same way as standard firmware IWE package.
  • Page 102: Identifying Configured Ecu

    SISU EEM3 Gen-set MTU ADEC J1939 Deutz EMR3 Cummins CM850 Iveco Vector MAN MFR VM Marine VM Industrial GM SECM ISUZU ECM E-control ECU Standard J1939 engine InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 103: Values Read From Ecu

    SAE Truck and Bus Control and Communications Network Standards Manual, SAE HS-1939 Publication Or refer to corresponding engine manufacturer’s ECU error codes list. Complete list of text diagnostic messages for each ECU can be found in Comap Electronic Engines Support manual.
  • Page 104: Connection Description

    MAINS C.B. FEED-BACK GEN C.B. FEED-BACK CONTROL SIGNALS ALARM READY TO LOAD PRESTART MAINS C.B. GEN C.B. BO ECU PwrRelay BO ECU CommOK (EDCIII) / ECU CommError (EMSII) FUEL LEVEL InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 105 REMOTE OFF ACCESS LOCK EMERGENCY STOP MAINS C.B. FEED-BACK GEN C.B. FEED-BACK CONTROL SIGNALS ALARM READY TO LOAD PRESTART MAINS C.B. GEN C.B. + 24 V DC FUEL LEVEL InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 106: Cummins Engines With Modbus Communication

    RS232/RS485 converter (see following diagram) set up: Data format settings (SW1) 11 bits (1 start bit, 8 data bits, 2 stop bits) Baud rate settings (SW2) 9600 bps (more info available on http://www.advantech.com/products/Model_Detail.asp?model_id=1-D6FLH) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 107 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 108 Phone number modification – TelNo/Addr Ch1/2/3/4 setpoints Phone number modification is completed when two space symbols one after another are inserted and the second space is confirmed by pressing ENTER button. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 109: Background Of The Sensor Calibration

    VDO Fuel % Hint: When measured value is 6% out of range the Sensor Fail FLS is detected. You can find detailed information on sensores in LiteEdit Reference Guide. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 110: Function Description

    Not Ready RPM < 2, Oil pressure not detected, Vgen Ready < 10V, D+ not Active no shutdown alarm active, other than OFF Mode selected Prestart Prestart time elapsed STARTER on Cranking InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 111 Stop (Stop fail) if all generator parameters OK and Min Stab Time elapsed, indicates that GCB is possible to close. In AUTO Mode closes in this moment GCB automatically. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 112: Aut Mode

    Mains operation then after Transfer Del MCB CLOSE/OPEN on and then engine stop sequence performed Mains failed means mains over/under -voltage, over/under -frequency, voltage assymetry (preset delay must elapse) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 113: Test Mode

    Relation between Mains fail and MCB and start of gen-set MCB Opens On = MAINSFAIL: Mains fail is detected as Mains <V, Mains >V, Mains V Unbal, Mains <Freq, Mains >Freq. After detection MCB is opened. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 114: Relation Between Mains Return And Mcb

    Conditions: AUTO Mode, Mains =off, MCB = opened, GCB = closed, gen-set loaded. Mains returns: GCB opens (according 3., MainsReturnDel), MCB closes (Transfer Del) GCB opened MCB closed Fwd Return Del InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 115 Situation 2: ReturnFromTEST=MANUAL, Mains =OK, MCB is closed, gen-set is running. Press MCB on/off -> MCB opens, GCB closes (Transfer Del), gen-set is running loaded. MCB opened GCB closed Fwd Return Del InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 116: Alarm Management

    Mains failure detection depends on Auto mains failure setpoints (levels and delays) adjusting. When the mains failure comes up, mains circuit breaker is opened. Possible mains failure reasons: List of possible events InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 117: Voltage Phase Sequence Detection

    Sensor Fail detection Sensor Fail Fls is detected when measured value is 6 percent out of range. Controller screen displays in this case string #### instead measured value. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 118 BO GCB close/open Time delay closed 5 or 2 sec BI GCB feedback active Alarm: GCB fail Hint: You can solve state of MCB fail by pressing Fault Reset button. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 119: Gen-Set Operation States

    Forward return break delay. Delay between GCB opening and MCB closing List of possible events Information on binary Events Protection output available (See Description specification type list of Binary outputs) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 120 This alarm is activated when Eart Fault value exceeds Earth Fault Sd limit for at least Earth Fault Del period. Sd Overspeed The protection comes active if the speed is greater than Overspeed setpoint. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 121 Volt Unbal Sd setpoint. Mains >, < Freq The generator frequency is out of limits given by Gen >Freq Sd and Gen <Freq Sd setpoints. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 122 Alternate Cfg group. MAutDetecFail Mains autodetection failed suitable configuration not found in Alternate Cfg group. AlterCfg 1..3 Act Successful autodetection. (chosen configuration group indication) *Only when ECU is configured InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 123: History File

    IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM) BOM* IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM) BIOE* Extension plug-in module inputs and/or outputs *Depends if enabled in configuration (see more details in LiteEdit-4.4-Reference Guide.pdf) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 124: Init Screens

    User Interfaces. Last value displeyed on screen is DiagData, which is internal ComAp information in case of FW or unit problems, which helps ComAp to analyze the root cause and find a proper solution.
  • Page 125: Operator Interface Amf

    FUEL PUMP button. While this button is pressed FUEL PUMP is activated until Fuel Pump OFF level is reached. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 126 PAGE button. Use this button to switch over display pages. See Display Screens and Pages Structure chapter below this table for more details. UP button. Use this button to move up or increase a value. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 127 DOWN button. Use this button to move down or decrease a value. ENTER button. Use this button to finish editing a setpoint or moving right in the history page. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 128: Display Screens And Pages Structure

    0 Switched On Enter AlarmList Emergency Stop Page History and Setpoints pages are available only when you choose Engineer interface (not User). See Controller Information Screen subchapter below. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 129: Alarms

    100 OC 4 FMI alarm Fault deactivation reset ECU AlarmList > 0 OC 0 FMI ECU AlarmList page is available only when ECU is configured. Earth Fault Protection Test & InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 130 BO: Breaker Trip TEST ! Not ready MainsFlt 0 . 00 R PM No Timer 0 kW InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 131: Setpoint Change

    Date/Time Enter Page >EnterPassword Changepassword Enter Enter Page Lost password? Display the >EnterPassword InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 information screen containing AMF26-P-2.4 Reference Guide.pdf Changepassword serial number password decode number as described in the chapter below and send them to your local distributor.
  • Page 132: Controller Information Screen

    Pwd. dec.: 1234567890 Page Display Contrast Adjustment TEST ! Not ready MainsFlt 0.00 TEST ! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 No Timer AMF26-P-2.4 Reference Guide.pdf Not ready 0 kW Enter + MainsFlt 0.00 TEST ! Enter +...
  • Page 133: Remote Control And Data Logging

    Direct connection to the PC IL-NT can be connected directly with PC via optional IL-NT RS232 interface. Use the recommended ComAp AT-LINK CABLE 1.8M or cross-wired serial communication cable with DB9 female connectors and signals Rx, Tx, GND for RS232 connection.
  • Page 134: Pc Software - Liteedit

    The RS232 or USB interface uses COM1 port of the controller. The RS485 uses COM2. PC software - LiteEdit On the PC (for direct or modem connection) has to be installed the ComAp’s software package LiteEdit. (based on Windows 95 or newer platform)
  • Page 135 Engine Params Cooling Time 120 s 8258 3600 Unsigned 16 Engine Params Stop Time 60 s 9815 240 Unsigned 16 Engine Params Fuel Solenoid DIESEL 9100 String list InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 136 4,0 s 8283 60,0 Unsigned 16 Gener Protect Amps Unbal Sd 50 % 8284 200 Unsigned 16 Gener Protect Amps Unbal Del 5,0 s 8285 600,0 Unsigned 16 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 137 8771 900 Unsigned 16 Extension I/O IOM AI3 Wrn 0 U6 8764 -100 10000 Integer 16 Extension I/O IOM AI3 Sd 0 U6 8768 -100 10000 Integer 16 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 138 EF Prot Test 11630 String list Man Operations RestoreDefault 11624 String list Alternate Cfg Config Switch Manual 12045 String list Alternate Cfg NominalPower1 39 kW 12046 5000 Unsigned 16 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 139 Integer 16 Generator Gen kVAr L3 5,0 kVAr 8529 Integer 16 Generator Gen Output 153,0 kVA 8565 Integer 16 Generator Gen kVA L1 51,0 kVA 8530 Integer 16 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 140 [1111001] 8235 Binary 16 Controller I/O Bin Outputs [1111000] 8239 Binary 16 Controller I/O GSM SignalLvl 11895 Unsigned 16 Extension I/O IOM AI1 10 U4 8978 Integer 16 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 141 Application 8480 Unsigned 8 IL Info FW Branch 8707 Unsigned 8 IL Info PasswordDecode ##### 9090 Unsigned 32 Date/Time Time ##### 24554 Time Date/Time Date ##### 24553 Date InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 142: Remote Communication

    Controller address is unique controller identification number located in setpoint group Basic Settings : Contr addr [1 to 32]. Syntax: XX … controller address [1 to 32] Example: Message is addressed to controller with address 5. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 143 Password is a number in range 0 to 65535 and is valid for all rest of SMS. Syntax: p PPPP (or pPPPP) … command password PPPP… Example: #5:accesscode 1234, w 8252 144 Setting password before adjusting protected setpoint. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 144 1. Answer message contains at most eight items of Alarm list. 2. Alarm list is not separated to more messages. 8. Time delay Insert time delay before serving next part of SMS command. Syntax: … command InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 145 Answer message is sent to the originator phone number. Tree dots at the end of message indicate separation and next following message. Example: #5:accesscode r8252,w8252 100,r8252 answer message InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 146 Setpoints Stringlist type (e.g. Controller Mode) is read as string and adjusted as index of string item in string list. e.g. Controller Mode: Read value Write value [as [as string] index] TEST InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 147: Event Messages Description

    5896:30 Load on Mains 5896:30 AMF Stop Hint: Event message is sent, if there is no other event. within 30s, any additonal delay could be caused by local provider. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 148: Recommended Isdn Modem

    Fail to follow these instructions (power supply active only in controller or only in module) can lead to module or controller failure! InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 149 1. You will need one of supported ComAp controllers (IL-NT/IC-NT/ID-Lite), IL-NT-GPRS, antenna, SIM card with GPRS service and optionally IL-NT-RS232 or IL-NT-S-USB module. Firmware supporting IL-NT-GPRS module is IL-NT-WSUP 1.0 or selected customer branches (contact support@comap.cz for details). It is available here: http://www.comap.cz/products/detail/IL-NT-GPRS/support/software/...
  • Page 150 „AirGate IP“ = 80.95.108.26. This will save significant data amount needed for translation of Airgate server IP address. In case of changing the server IP address this settings has to be updated or returned to default „airgate.comap.cz“. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 151 Bad answer to complement initialization string Not possible to read GSM signal strength CDMA modem not detected No CDMA network Unsuccesful registration to CDMA network Only running communication is needed to indicate InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 152 Controller registered, waiting for authorization Not possible to register, controller blacklisted Not possible to register, server has no more capacity Not possible to register, other reason Controller registered and authorized InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 153: Il-Nt-Rd Remote Display Software

    Choosing the wrong type of firmware may result in non-functional controller. Press "OK" button to programm the firmware to the controller. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 154: Il-Nt-Rd Wiring

    Direct RS232 connection HW module: IL-NT-RS232 Master controller settings: ControllerAddr = 1..32 COM1 Mode = DIRECT Up to 2 meters: It is recommended to use our standard AT-LINK cable. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 155 RxD 2 3 TxD TxD 3 2 RxD GND 5 5 GND Remote RS485 and/or direct RS232 connection HW module: IL-NT-RS232-485 Up to 1000 meters (only with RS485): InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 156 38400 or 56000 bps. Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR connected) after switch on. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 157: Function Description

    PAGE button for 3 seconds. SW compatibility IL-NT-RD sw. version 1.2 is compatible with IL-NT-AMF26-P-1.0. Some of the future IL-NT-AMF26-P versions may require upgrade of the IL-NT-RD software. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 158: Maintenance

    4. The battery is located in a holder on the circuit board. Remove the old battery with a small sharp screwdriver and push with a finger the new battery into the holder. Use only CR1225 lithium battery. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 159 6. Plug the modules back into the slots. 7. Power the controller on, adjust date and time and check all setpoints. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 160: Technical Data

    * With optional IL-NT-EFCPM/IL-NT-EFCPM2 module ** With optional communication plug-in module Y -Available N -Not available Generator protections ComAp gen-set controllers provide following range of generator protections. For each protection adjustable limit and time delay are available. Comparison table with ANSI codes: ANSI IL-NT...
  • Page 161: Language Support

    IL-NT in firmware version 2.3 supports following language code pages Code page Language Windows code West European languages Windows 1252 Chinese GB 2312 Turkish Windows 1254 Japanese Windows 932 Russian Windows 1251 East European languages Windows 1250 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 162: Power Supply

    12 A Voltage inputs Measuring voltage range 0 – 277 VAC phase to neutral 0 – 480 VAC phase to phase Maximal measured voltage 340 VAC phase to neutral InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 163: Binary Inputs And Outputs

    Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length and 32 iS-COM units connected: Nominal Velocity of Propagation min. 75% (max. 4,4 ns/m) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 164: Il-Nt Rs232 Interface (Optional Card)

    Maximum Speed Up to 57,6 kBd (DIRECT), 38,4kBd Analog modem, 9,6 kBd digital modem, 57,6 kBd (MODBUS) Hint: This module is supported with SW version IL-NT 1.3 and newer. InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 165: Il-Nt S-Usb Interface (Optional Card)

    9,6 kBd digital modem, 57,6 kBd (MODBUS) Use only shielded A-B USB cables up to 5m length. Recommend USB cable: USB-LINK CABLE 1.8M – ComAp A-B USB cable. Hint: With SW version IL-NT 1.2 and older, the communication speeds are 19,2kBd (STD/DIRECT),...
  • Page 166: Igs-Ptm

    1mV out of measured value Current measurement tolerance 2,5 % 0,5mA out of measured value IGL-RA15 Power supply Voltage supply 8-36V DC Consumption 0,35-0,1A (+1A max horn output) InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...
  • Page 167: Ig-Ib

    95 x 96 x 43 mm , DIN rail (35 mm) mounted Interface to controller RS232 Interface to modem RS232 Interface to Ethernet RJ45 (10baseT) Operating temperature -30..+70 Storage temperature -30..+70 InteliLite AMF26-P, SW version 2.4, ©ComAp – January 2016 AMF26-P-2.4 Reference Guide.pdf...