Fire Safety; Smoke Alarms - Envirovent KIT-PIV-SMOKE-200 Installation Manual

Piv & miv air source / inline ventilation unit

Advertisement

Fire Safety

Fire Kits
For installations with a floor more than 4.5m above ground, a
compatible fire kit must be fitted. The kits listed below contain all
the extra parts and instructions required:
Order Code
Description
KIT-PIV-SMOKE-200
200mm fire-rated diffuser for PIV units only
KIT-MIV-SMOKE-125
2x 125mm fire-rated diffusers for MIV units only

Smoke Alarms

For installations with a floor more than 4.5m above ground, the unit
must be wired into a smoke alarm in order to switch the unit off upon
the detection of smoke.
The unit can be wired into an existing smoke alarm (check compatibility
with the smoke alarm manufacturer). All wiring should be completed
by a competent person.
To test the installation, press the TEST button on top of the smoke alarm
and keep it pressed until the PIV unit switches off (LEDs on the board
go out).
DO NOT
AFTER INSTALLATION THE END USER SHOULD
KEEP THIS GUIDE FOR FUTURE REFERENCE
THROW AWAY
14