Product Installation Guidelines
®
CliniLever
PRODUCT CODES:
-
102.12.22.03
-
102.12.21.03
-
102.12.12.03
-
102.12.11.03
-
102.13.21.03
-
102.13.11.03
-
102.14.12.03
SPECIFICATIONS
®
The CliniLever
product range is primarily used for hand washing applications in hospitals, aged care
facilities, schools and in-home care.
®
CliniLever
products provide state of the art features to comply with the latest healthcare guidelines.
Easy to operate dual levers for on/off, hot and cold temperature control simplify hand washing procedures.
®
All CliniLever
products provide laminar flow (not aerated).
Our highly sought after lever design is easily operated with elbows or wrist to avoid hand contact.
The main body is made of solid dezincification resistant (DR) brass rod, with a DR brass gooseneck outlet.
Quick action SBA's includes brass jumper valve / ceramic cartridge component, with red and blue indicator
button on 80mm or 150mm lever action handles.
Lead Safe™ brass construction*
IMPORTANT: All CliniLever
premises in good working order.
*Our Lead Safe™ product range is compliant with the Lead-Free Requirements of the NCC 2022 Vol. Three, Clause A5G4(2) and NSF/ANSI 372.
**
Any flow controller incorporated in the outlet to be tightened to prevent removal by hand. As Per AS3718.
WARNINGS: Special attentions to be paid on notes, photos, images, or drawings of
assembly steps marked with the warning symbol.
TECHNICAL DATA
Inlet
Outlet
Headwork
Working Pressure Range (kPa)
Working Temperature Range (°C)
Nominal Flow rate (LPM)
Construction
Finish
NOTE: Galvin Engineering continually strive to improve their products. Specifications may change without
notice.
TOOLS REQUIRED
Power drill
© Galvin Engineering Pty Ltd
CP-BS Lead Safe Hospital Basin Fixed Sets
®
healthcare taps are tested in accordance with AS/NZS 3718 and leave our
102.12.12.03, 102.12.11.03, 102.13.11.03
102.12.22.03, 102.12.21.03, 102.13.21.03, 102.14.12.03
Spanner or adjustable crescent
Version 1, 7 June 2024, Page 1 of 5
Document No.: 001.00.10.03
½" CU/BSP
Laminar Flow
Jumper Valve
Ceramic Disc
Min
50
Max
500
Min
5
Max
65
5.5
Brass
Chrome
Copper tube cutter

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CliniLever CP-BS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Galvin Engineering CliniLever CP-BS

  • Page 1 Working Pressure Range (kPa) Working Temperature Range (°C) Nominal Flow rate (LPM) Construction Brass Finish Chrome NOTE: Galvin Engineering continually strive to improve their products. Specifications may change without notice. TOOLS REQUIRED − − − Power drill Spanner or adjustable crescent Copper tube cutter ©...
  • Page 2: Pre-Installation

    102.12.21.03/102.12.11.03 INSTALLATION INSTALLATION COMPLIANCE: Galvin Engineering products must be installed in accordance with these installation instructions and in accordance with AS/NZS 3500, the PCA and your local regulatory requirements. Water and/or electrical supply conditions must also comply to the applicable national and/or state standards.
  • Page 3 − Once secured, connect the hot and cold water. − Open the lever handles and ensure that there is flow from both hot and cold inlets. − Inspect the tap and check for any leaks. © Galvin Engineering Pty Ltd...
  • Page 4: Troubleshooting

    7. Replace the cartridge and hand-tighten back into the body. 8. Re-assemble top assembly. Follow the product installation guidelines for the relevant product to 8. Follow the product installation guidelines for the re-assemble. relevant product to re-assemble. © Galvin Engineering Pty Ltd...
  • Page 5: Warranty

    WARRANTY Version 2, 7 June 2024, 5 of 5 Galvin Engineering products are covered under our Manufacturer's Warranty. Galvin Engineering products must be installed in accordance with the installation instructions and in accordance with AS 3500 and NCC Volume Three, relevant Australian Standards and local authorities applicable to product being installed.