Galvin Engineering CliniMix 190.88.00.09 Installation Manuallines

Emergency shower thermostatic mixing valve

Advertisement

Quick Links

Product Installation Guidelines & Scope of Use
®
CliniMix
Emergency Shower Thermostatic Mixing Valve
Product Codes
CliniMix
190.88.00.09
Thermostatic Mixing Valve
190.49.00.90
CliniMix
(190.88.00.09
Mixing Valve and SS Cabinet
+
190.93.00.10)

1. Specifications

®
The CliniMix
Emergency Shower Thermostatic Mixing Valve is designed to be paired with Safety
Showers and, with limitations, Eye/Face wash units. In addition to these instructions, the valve must be
installed subject to the requirements of the relevant regulatory authorities.
Ensures high stability of mixed water temperature even under varying inlet conditions.
Ensures rapid termination of mixed outlet flow if there is a failure in either the cold or hot water supply, and
allows for continuous cold water flow through the bypass in the event of hot water failure, guaranteeing an
uninterrupted supply for emergency situations.
Suitable for installation into AS3500 compliant systems with hot water temperature as low as 55°C
Fitted with a tamper resistant temperature adjustment mechanism
WARNINGS: Special attentions to be paid on notes, photos, images, or drawings of
assembly steps marked with the warning symbol.

2. Table of Contents

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
© Galvin Engineering Pty Ltd
®
Emergency Shower
®
Safety Shower Thermostatic
Version 1, 22 October 2024, Page 1 of 16
Document No: 001.30.30.00
+
10
1
1
2
2
3
3
4
4
5
7
8
9
9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CliniMix 190.88.00.09 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Galvin Engineering CliniMix 190.88.00.09

  • Page 1: Table Of Contents

    2. Table of Contents Specifications Table of Contents Technical Data Safety Flow Sizing Graph Dimensions Tools Required Installation Requirements Installation (Valve) Installation (Cabinet) Commissioning of the Valve Temperature adjustment Locking the Temperature Settings Shut Down Test © Galvin Engineering Pty Ltd...
  • Page 2: Technical Data

    Static Inlet Pressures Hot and Cold Inlet Pressures (kPa) 1000 NOTE 1: Notwithstanding the above, compliance with AS/NZS3500 must be maintained. NOTE 2: Galvin Engineering continually strive to improve their products. Specifications may change without notice. 4. Safety The CliniMix ®...
  • Page 3: Flow Sizing Graph

    Product Installation Guidelines & Scope of Use Version 1, 22 October 2024, Page 3 of 16 5. Flow Sizing Graph 6. Dimensions Figure 1 - 190.88.00.09 © Galvin Engineering Pty Ltd...
  • Page 4: Tools Required

    (refer to Technical Data), a suitable temperature limiting valve must be fitted upstream of the inlet fitting. • Tapware must be installed in accordance with the provisions of AS/NZS 3500. Installations not complying with AS/NZS 3500 may void the product and performance warranty provisions © Galvin Engineering Pty Ltd...
  • Page 5: Installation (Valve)

    Version 1, 22 October 2024, Page 5 of 16 9. Installation (Valve) INSTALLATION COMPLIANCE: Galvin Engineering products must be installed in accordance with these installation instructions and in accordance with AS/NZS 3500, the PCA and your local regulatory requirements. Water and/or electrical supply conditions must also comply to the applicable national and/or state standards.
  • Page 6 • Ensure inlet and outlet pipe connections are not permanently fixed to the mixing valve for easier maintenance and servicing Once the valve is installed, proceed to commissioning. © Galvin Engineering Pty Ltd...
  • Page 7: Installation (Cabinet)

    30mm and after fitting the valve there is approximately 54mm available between the bottom of the cabinet and the valve. 1. Remove the screws and front cover as 2. Secure cabinet to the wall using the 4 x shown Ø6mm holes as shown. © Galvin Engineering Pty Ltd...
  • Page 8: Commissioning Of The Valve

    It is essential to carefully review the entire procedure before commissioning the valve. To check and adjust the valve’s outlet mixed temperature, you will require a calibrated digital thermometer with rapid response time and maximum temperature hold. © Galvin Engineering Pty Ltd...
  • Page 9: Temperature Adjustment

    We recommend using the GalvinSafe Shower & Eye Wash Testing Kit 190.95.90.90 (available from Galvin Engineering) in checking the flow rate. Important: the testing must be performed on all outlets individually (example: on a shower and Face/Eye wash) 7.
  • Page 10: Shut Down Test

    CLR), checked for physical damage and then thoroughly rinsed with clean water. Re-install the strainers into the valve. Ensure bypass assembly and compression nuts are tightened well to prevent leaking (see Chapter 9 for installation details). © Galvin Engineering Pty Ltd...
  • Page 11 Disassemble pilot valve assembly as shown in Figure 13. Inspect and check non-return valve located in pilot valve assembly. Check operation and flush under running water as per previous steps. Non-return Valve Figure 12 Non-return Valve Figure 13 © Galvin Engineering Pty Ltd...
  • Page 12 In addition to the Annual Maintenance and Servicing, the Thermostatic Element of the mixing valve must be replaced at intervals not exceeding 5 years. The Thermostatic Element (part code 201.90.41.90) will be required. Ensure a silicone-based lubricant suitable for use with potable water is used when re-greasing O-rings. © Galvin Engineering Pty Ltd...
  • Page 13: Spare Parts

    Emergency Shower Thermostatic Mixing Valve Piston Element Kit 201.90.41.90 ® CliniMix Emergency Shower Thermostatic Mixing Valve Inlet Fitting Kit 201.90.42.90 ® CliniMix Emergency Shower Thermostatic Mixing Valve Bypass Assembly Kit 201.90.43.90 ® CliniMix Emergency Shower Thermostatic Mixing Valve Outlet Fitting Kit 201.90.44.90 © Galvin Engineering Pty Ltd...
  • Page 14: Commissioning, Service And Maintenance Report

    Checked Checked Checked Checked Checked Strainers Clean Replaced Replaced Replaced Replaced Replaced Checked Checked Checked Checked Checked Non-Return Valve Replaced Replaced Replaced Replaced Replaced O-Ring Replacement Replaced Thermostatic Element/Piston Replaced Assembly Replacement Authorised Tester’s Signature: © Galvin Engineering Pty Ltd...
  • Page 15: Minimum Flow Rate To Ensure Stable Operation (L/Min) Min

    Product Installation Guidelines & Scope of Use Version 1, 22 October 2024, Page 15 of 16 Troubleshooting PROBLEM CAUSE RECTIFICATION Hot and cold supplies are fitted Refit the valve with Hot/Cold supplies fitted to to the wrong connections the correct connections. Clean the valve ensuring debris is removed Valve contains debris.
  • Page 16: Warranty

    Warranty Galvin Engineering products are covered under our Manufacturer's Warranty. Galvin Engineering products must be installed in accordance with the installation instructions and in accordance with AS 3500 and NCC Volume Three, relevant Australian Standards and local authorities applicable to product being installed.

This manual is also suitable for:

Clinimix 190.49.00.90

Table of Contents