6.11

Battery Test Page

The ability to run a remote batter self-test can be found on this page. Battery self-tests are a valuable main-
tenance tool to determine whether the battery string has the capacity to run the load during Inverter oper-
ation. This test does not perform conductance testing and only uses battery string voltage as a reference to
determine whether test pass or fail. If the test is successful for the duration of the user selectable time, the
tests passes, and it may be assumed that the current condition of the overall battery string is sufficient for
battery backup. Otherwise, the test is deemed a fail and the condition of each battery should be checked
using a hand-held battery tester or may be monitored with a full featured battery management system that
reports the true condition and age of each battery in the string. Certain conditions are required prior to per-
forming a remote battery self-test. Any condition that is not met will be listed on this page, such as present
alarms or incorrect UPS mode, and will prevent a self-test from being performed until corrected. The Battery
Test Status will update every 10 seconds to allow the user to monitor the battery string voltage.
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
40
© Multilink Inc. 2020 • All Rights Reserved