Multilink EP 1100 Installation & Operation Manual

Line interactive ups
Table of Contents

Advertisement

Quick Links

EP 1100
EP1100 Line Interactive UPS
Installation & Operation Manual
Documented Power Supply Models
The following uninterruptible power supply models, with their part numbers, are documented
by this instruction manual. These power supply and their respective packages may be references
using the part numbers listed below.
MODEL NUMBER
PART NUMBER
INPUTS
EP1100 120/60/48 UPS
010-037-10
120VAC/60Hz; 48VDC
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
© Multilink Inc. 2020 • All Rights Reserved

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EP 1100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Multilink EP 1100

  • Page 1 These power supply and their respective packages may be references using the part numbers listed below. MODEL NUMBER PART NUMBER INPUTS EP1100 120/60/48 UPS 010-037-10 120VAC/60Hz; 48VDC Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 2: Table Of Contents

    Section 5: Startup and Operation 5.01 Front Panel LCD Menus ....................................21 5.02 LCD Screen ..........................................21 5.03 LCD Menu Tree ........................................21 Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 3 Grounding Kits ........................................52 Section 9: Maintenance and Troubleshooting 9.01 Preventative Maintenance .....................................53 9.02 Troubleshooting ........................................54 Section 10: EP1100 UPS Specifications Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 4: Section 1: Critical Safety Issues

    Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 5: Emergency Shutdown Procedures

    Internal DC circuits will retain harmful electrical charge after disconnecting both power sources from the UPS. Only trained personnel should be permitted to han- dle this UPS. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 6: Ground Fault Protection

    This equipment generates, uses, and can radiate radio frequency energy and, if not installed in accordance with this instruction manual, may cause harmful interference to radio communications. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 7: Battery Safety Issues

    1 IEC 60900: Live Working – Hand Tools for Use Up to 1000VAC and 1500VDC ASTM F-1505: Standard Specification for Insulated & Insulating Hand Tools Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 8: Section 2: Introduction

    Short circuit conditions will disconnect the inverter and open the input/output circuit breaker. In the event a short circuit occurs, the unit will have to be manually reset. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 9: Automatic Voltage Regulation With Buck/Boost

    • Compliant UPS product per IEC Standard 60950-1, UL1778, and FCC Part B • Complies with EMI/RFI limits of Standards EN 55022 and EN 55024. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 10: Unpacking And Inspection

    Multilink representative immediately. Be sure to retain the original shipping carton and all packing material for the power supply until it is certain that a warranty return will not be required.
  • Page 11: Section 3: Front Panel Controls, Connections And Indicators

    Reserved for future use. User Input User Inputs for Batt-Test, Door Alarm, and AC Shutdown. Reserved Reserved for future use. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 12: Indicators

    Qual or Standby modes. If the Red LED is flashing, there is an alarm that is present. If it is on, there is a fault present. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 13: Rotatable Front Panel

    90° Multilink EP1100 In:120V Out 120V Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 14: Section 4: Installation Setup

    Multilink Inc. Refer to the OPTIONS section of these instructions for further information. In all installations, the following conditions apply and must be observed: •...
  • Page 15: Placement In The Enclosure

    2. Operate the both Input circuit breaker and Battery circuit breaker on the front panel of the power supply to the OFF (O) position. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 16 White – AC Utility Line and Output Neutral Terminal Block Buses d. Green – AC Utility Line and Output Ground Terminal Block Buses Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 17: Battery Placement And Wiring

    Additionally, proper lifting tools and techniques must always be used during battery installation to avoid personal injury or equipment damage. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 18: Battery Installation Procedure

    (-); red terminal is positive (+). 5. Attach the ring lug to the negative post on the 48VDC battery. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 19: Care And Maintenance Of Batteries

    Please refer to the battery manufacturer’s instructions for maintenance. 2 NO-OX-ID-“A-Special” is a registered trademark of Sanchem, Inc, Chicago, IL Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 20: Section 5: Startup And Operation

    9. Verify the Alarm LED is not flashing. If so, investigate the cause of the alarm and correct the alarm. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 21: Front Panel Lcd Menus

    These menus will be described below. Press the “Select” button to select a menu, the item dis- played, or press the “Cancel” button to return to the previous menu or exit a configuration state. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 22: Menu Options And Descriptions

    Use the Scroll button to view items. Use the Cancel button to return to the prevous menu. Each parameter will be descirbed below. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 23: Controls Menu

    Force Inverter: Disable by default, may be turned on to force inverter operation. BYPASS Bypass: off by default, may be enabled by user to bypass Inverter and charger operation. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 24 Daylight: Adjust clock based on date of daylight savings time. TIMER: 120 M Timer Relay: Time delay until Timer relay closes. 0-240 in 5 min increments. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 25: Faults Menu

    • Battery Over Voltage – The battery string voltage is too high. Test the condition of each battery in the string. • Temp Fault – The UPS is being operated outside of its rated operating temperature. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 26: Alarms Menu

    • Batt Temp Low – The battery temperature is below the rated operating conditions. • Fan Alarm – The fan has failed. Contact Multilink Engineering Support. • Input Brkr Open – The AC input breaker is open.
  • Page 27: Events Menu

    C6: Reserved for future use. C7: USER INPUT C7: An external input has been activated. C8: RESERVED C8: Reserved for future use. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 28: Section 6: Status Monitoring

    10. Open a preferred web browser and enter the IP address shown. Navigate to any of the pages indexed on the left side of the webpage to view or modify operating parameters. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 29: Webpage Description

    UPS. Parameters that are measured by the UPS are updated automatically on the webpage every 10 seconds. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 30: Webpage Navigation

    The default username is “user” and the default pass- word is “multilink”. If the incorrect combination has been entered, the user will be prompted. It is encour- aged to change the user and password information upon login of each EP1100. If a mistake has been made when changing the username and password, contact a Multilink representative for information on how to correct this issue.
  • Page 31: Main Product Information Page

    MAC address, and unit temperature as shown on this page. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 32: Log Out And User/Password

    Submit to avoid errors. NOTE: both the username and password are case sensitive. Record the username and password combination in a safe place to prevent unauthorized access. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 33: Alarm Information Page

    Pgs. 25-26 of this user manual will be shown on this page. Once the alarm or fault is cleared, the alarms and faults tables with display “no alarms reported” and “no faults reported”, respectfully. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 34: Control Options Pages: Ups Control Options

    When clicked, the button will only become available when the events log has been reset, which may take up to 60 seconds, depending on the numbers of events. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 35 Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 36: Control Options Pages: Other Control Options

    Relay Timer (mins): Timer delay in minutes before the C4 Timer dry-contact relay is energized. Adjustable between 0 and 240 minutes. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 37 Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 38: Operation Parameters Page

    Output voltage and frequency, as well as output current draw and total output power consumption are visible on this page. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 39: Battery And Inverter Parameters Page

    (Bulk, Equalize, Float, and OFF), battery temperature, as well as Inverter runtime. Inverter runtime is calculated at the start of a new Inverter mode event and displays 0 minutes by default. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 40: Battery Test Page

    UPS mode, and will prevent a self-test from being performed until corrected. The Battery Test Status will update every 10 seconds to allow the user to monitor the battery string voltage. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 41: Relay Reporting Page

    These relays are self-correcting, depending on the purpose of each relay as they are defined. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 42: Event Reporting Page

    The latest event is displayed on the top of the stack. The table may be copied and pasted directly into a spreadsheet for easy editing and printing. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 43: Time Set Page

    It is encouraged that when the format of the date and time changes to clear the events log. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 44: Site Information Page

    The city and state, providence, or region may be included as well. Be sure to click Submit to save all changes. The user will be prompted when changes have not yet been saved. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 45: Ip Configuration Page

    EP1100 be configured and verified by the user prior to deployment in the field. Be sure to click Submit to save all changes. The user will be prompted when changes have not yet been saved. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 46: Snmp Page

    (NMS). A proprietary MIB must be used with the NMS to enable SNMP objects to be recognized and information to be passed to the NMS. This MIB is available on Multilink’s website or by contacting ENGSupport@gomultilink.com. SNMP versions v1, v2c, and v3 are built-in, with v2c enabled be default.
  • Page 47 Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 48 Traps are automatically sent upon an event to the user specified trap receiver. Some traps occur periodically until they are resolved. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 49: Email Notification Page

    The SMTP Status will update to Success and the recipients shall receive a test email. Be sure to check the spam or junk folders if an email has not been received. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 50: Serial Connection Setup

    The DB-9 serial port located on the front of the EP1100 is intended to be used by the factory only and does not provide users with options for monitoring or controlling the UPS. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 51: Section 7: Power Supply Shutdown

    8.03 Battery Heater Mat In harsh climates where freezing temperatures can shorten the life of the batteries, Multilink has designed a battery mat option for various battery string and cabinet shelf applications. 176-003-10: 2-Battery Heater Mat with thermostat for dual battery shelf cabinets. 13” X 14”...
  • Page 52: Transfer Switch Options

    If desired or required by state law, grounding kits are available to provide an isolated grounding point on the EP1100 UPS. 035-006-11: Ground lug kit. Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 53: Section 9: Maintenance And Troubleshooting

    • Verify the power supply is in its normal mode of operation as indicated by the LCD • Close and lock the enclosure Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 54: Troubleshooting

    This troubleshooting guide has been designed to help quickly locate and resolve common problems. The table assumes normal operation and configuration of the UPS at any given time. If the problem cannot be resolved, replace the power supply with a known good unit or call Multilink Inc. for support. Operating Conditions...
  • Page 55: Section 10: Ep1100 Ups Specifications

    Dry Contact Relays Switching power 60 watts, 62.5VA Switching voltage 220Vdc, 250Vac Minimum contact rating: 10mVdc, 10μA Switching current Carrying current Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com © Multilink Inc. 2020 • All Rights Reserved...
  • Page 56 Multilink, Inc 580 Ternes Ln Scan Elyria, OH 44035 QR for Tel: (440) 366-6966 website. Fax: (440) 366-6802 facebook.com/GoMultilink1 twitter.com/GoMultilink youtube.com/GoMultilink North America Europe, Middle East & Africa Latin & South America Tel: +1 440 366 6966 Tel: +1 440 366 6966...