Using PID Control Mode

For details on the PID control settings, refer to the block diagram of the
Inverter's internal PID control or the block diagram of the Operator ana-
log speed reference.

PID Control Selection (n128)

Constant
No.
n128
PID Control Selection
Setting
0
Disabled.
1
Enabled: Deviation is subject to derivative control.
2
Enabled: Feedback signal is subject to derivative control.
3
Enabled: Frequency reference + PID output, and devia-
tion are subject to derivative control.
4
Enabled: Frequency reference + PID output, and feed-
back signal are subject to derivative control.
5
Enabled: Deviation is subject to derivative control.
6
Enabled: Feedback signal is subject to derivative control.
7
Enabled: Frequency reference + PID output, and devia-
tion are subject to derivative control.
8
Enabled: Frequency reference + PID output, and feed-
back signal are subject to derivative control.
Name
Function
6 Programming Features
Unit
Setting Range
-
0 to 8
Factory
Setting
0
PID Output
Characteristics
-
Forward
Reverse
(Reverse the
PID output.)
159