n116 Settings
Setting
0
1
• Stall Prevention during Deceleration (n092)
To prevent overvoltage during deceleration, the Inverter automati-
cally extends the deceleration time according to the value of the
main circuit DC voltage. When using an optional braking resistor,
set n092 to 1.
Setting
0
1
Note: If Stall Prevention during Deceleration is used with simple positioning
control, positioning will not be performed properly, so use a set value of
1.
134
Standard Selection Acceleration/Deceleration Time 1 or 2.
Automatic Selection Acceleration/Deceleration Time 2
(n021, n022).
Stall Prevention during
Deceleration
Provided
Not provided (with braking
resistor mounted)
Function
Controls the deceleration
time to prevent overvoltage.
Set
Decel
Time
Time