Con-
stant
No.
n057
n058
n059
100
Name
Multi-function Output
Selection 1
(Contact output ter-
minals MA-MB-MC)
Multi-function Output
Selection 2
(Open-collector out-
put terminals PHC1-
PHCC)
Multi-function Output
Selection 3
(Open-collector out-
put terminals PHC2-
PHCC)
Description
0: Fault
1: Operating
2: Frequency agree
3: Zero speed
4: Frequency detection (≥ Detection
level)
5: Frequency detection (≤ Detection
level)
6: Overtorque detection (NO contact
output)
7: Overtorque detection (NC contact
output)
8: Undertorque detection (NO con-
tact output)
9: Undertorque detection (NC con-
tact output)
10: Minor fault (Alarm is indicated)
11: Base blocked
12: Operating mode
13: Inverter operation ready
14: Fault retry
15: UV
16: Reverse run
17: Speed search
18: Data output from communica-
tions
19: PID feedback loss
20: Frequency reference loss
21: Inverter overheat alert (OH3)
22: Motor selection monitor
Same as constant 57
Same as constant 57
Fac-
tory
Set-
ting
0
1
2