Wiring - Omron NS10-TV Series Setup Manual

Ns-series ns-series
Hide thumbs Also See for NS10-TV Series:
Table of Contents

Advertisement

3-8-4

Wiring

This section describes the method for wiring the network communications cable to the Con-
troller Link Support Board.
Wiring the Communications Cable
Wire the communications cable to connect identical signals.
Precautions
for Safe Use
Connecting the Communications Cable
Connect the communications cable to the Controller Link Support Board after first connect-
ing it to the cable connector provided.
Use one of the twisted-pair cables listed below as the communications cable.
Li2Y-FCY2x0.56qmm KROMBERG & SHUBERT, De-
1x2xAWG-20PE+Tr.
CUSN+PVC
#9207
ESVC0.5x2C
ESNC0.5×2C-99-
087B
Precautions
for Safe Use
Reference
• Use the cable specified for the communications cable.
• Keep communications cables separated from power lines or high-tension
lines to prevent influences from electronic noise.
• Ground the shield of the communications cable at one end of the network.
Do not ground the shield at both ends.
• Do not connect the shield cable of the communications cable to a ground
that is also being used for power-system devices, such as inverters.
• Do not run wiring outdoors. If outdoor wiring is necessary, take protective
measures against lightening, such as underground wiring or wiring inside
pipes.
• Always turn OFF the power to PT before connecting the communications
cable or installing/removing the connector.
• Use the connector attached to the Controller Link Support Board.
Model
partment KOMTEC
DRAKA CABLES INDUSTRIAL
BELDEN
Bando Densen Co.
Nihon Electric Wire & Cable Co. Japanese company
• Use the cables listed above.
• Normal communications may not be possible if a communications cable
other than those listed above is used.
Terminals for the same signal on the Controller Link Support Board's connector are
connected internally.
The thickness of the ground wire connected to the Controller Link Support Board's
connector must be less than 2.5 mm
Connect to the network using the special connector provided with the Controller Link
Interface Unit.
3-8 Installing the Controller Link Interface Unit
Manufacturer
2
.
Remarks
German company
Spanish company
American company
Japanese company
3-55

Advertisement

Table of Contents
loading

Table of Contents