3-1 Installing the PT
Precautions
for Safe Use
Reference
3-6
This product conforms to shipbuilding standards. The shipbuilding standards
have conditions that may make them unusable depending on the location in
which the PT is installed. When using a PT on a ship, be sure to contact your
OMRON sales representative.
Shipping Standards (NK, LR, ABS, BV, DNV, KR, GL)
The conditions for use in locations other than the bridge or deck are as follows:
• The NS-series PT must be installed in a control panel.
• The control panel must be equipped with an air conditioner.
• The entire surface of the NS-series PT must be covered with electromag-
netic shielding (specified below) that is also grounded using conductive tape
(e.g., copper tape).
• Gaps in the door of the control panel must be completely filled or covered
with gaskets or other material.
• Gaps between the PT and the panel cutout must be completely covered with
conductive tape, such as copper tape, and the PT must be secured using
mounting brackets.
The conditions for use on a bridge (Class NK certification only) are as follows:
• The NS-series PT must be installed in a control panel.
• The control panel must be equipped with an air conditioner.
• The entire surface of the NS-series PT must be covered with electromag-
netic shielding that is also grounded using conductive tape (e.g., copper
tape).
• Gaps in the door of the control panel must be completely filled or covered
with gaskets or other material.
• Gaps between the PT and the panel cutout must be completely covered with
conductive tape, such as copper tape, and the PT must be secured using
mounting brackets.
• The following noise filter must be connected to the 0 to 24 VDC power line.
Electromagnetic Shielding
Manufacturer
Model
* Electromagnetic shielding reduces the permeability by approximately 50%.
Noise Filter
Manufacturer
Model
AC
DC power
supply
24 VDC
For the NS15 to provide IP65 oil-proof-type protection, at least the eight locations
shown in the following figure must be mounting with mounting brackets. There is a total
of 16 mounting locations.
SEIWA ELECTRIC MFG, Co., Ltd.
E09F-100, E09R13502P
Cosel
TAH-06-683
Noise Filter
Line
TAH-06-683
Load
PT
(Functional
ground)