Omron NS10-TV Series Setup Manual page 100

Ns-series ns-series
Hide thumbs Also See for NS10-TV Series:
Table of Contents

Advertisement

3-8 Installing the Controller Link Interface Unit
Indicators
Indicator
RUN
ERC
ERH
INS
SD
RD
LNK
3-46
Name
Color
Operating
Green
Communica-
Red
tions error
EEPROM error Red
Network par-
Yellow
ticipation
Send
Yellow
Receive
Yellow
Data link
Yellow
status
Lit
Normal operation.
Not lit
A Board operating error (watchdog timer error) occurred.
Lit
One of the following errors occurred.
• Communications error
• Same node address used twice (i.e., address duplica-
tion error)
• Hardware error
Not lit
Normal operation
Lit
One of the following errors occurred.
• EEPROM error
• EEPROM data link table error
• EEPROM routing table error
• EEPROM network parameter error
Not lit
No EEPROM error.
Lit
The Board is participating in the network.
Not lit
The Board is not participating in the network.
Lit
Sending data.
Not lit
Not sending data.
Lit
Receiving data.
Not lit
Not receiving data.
Lit
Participating in data link.
Flash-
Error in data link table setting.
ing
Not lit
Not participating in data link or data link inactive.
Meaning