Using Intelligent Output Terminals
4-6-5
Run Signal
1
[FW,RV]
0
b082
Output
start freq.
frequency
1
Run
ON
0
signal
Option
Terminal
Function
Code
Symbol
00
RUN
Run Signal
Valid for inputs:
11, 12, AL0 - AL2
Required settings:
(none)
Notes:
• The inverter outputs the [RUN] signal when-
ever the inverter output exceeds the start fre-
quency specified by parameter B082. The
start frequency is the initial inverter output fre-
quency when it turns ON.
• The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent
the negative going turn-off spike generated by
the coil from damaging the inverter's output
transistor.
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it
is in Run Mode. The output logic is active
low, and is the open collector type
(switch to ground).
t
State
Name
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example for terminal [11] (default
output configuration shown – see
page 135):
Inverter output
terminal circuit
Example for terminal [AL0],
[AL1], [AL2] (requires output
configuration – see page 199
and page 135):
See I/O specs on page 169
Section 4-6
Description
RUN
CM2
11
RY
Inverter logic
RUN
circuit board
AL0
AL1
AL2
Power
Load
supply
201