■ BCD Output Timing Chart
A REQUEST signal from a Programmable Controller or other external device is required to read BCD data.
Single Sampling Data Output
20-ms pulse min. (50 ms max.)
REQ.
MAX.MIN.
DATA
All data "High"
DATA
VALID
Approx.
30 ms
The data is set in approximately 30 ms from the rising edge of the
REQUEST signal and the DATA VALID signal is output.
When reading the data from a Programmable Controller, start
reading the data when the DATA VALID signal turns ON.
The DATA VALID signal will turn OFF 40 ms later, and the data will
turn OFF 16 ms after that.
• The K3HB BCD output model has an open collector output, so wired OR connection is possible
K3HB
(1)
Programmable
Controller
K3HB
(2)
DATA (including POL and
OVER) and DATA VALID
can be used in a wired OR.
RUN, HH, H, PASS, L, and
K3HB
LL are always output, with or
(3)
without a REQUEST signal.
Do not used a wired OR
connect for these signals.
Programmable Controller Connection Example
Digital Indicator
Connector pin No. (See note.)
1.COMMON
2.1
3.2
10
4.4
5.8
23.DATA VALID
24.RUN
25.COMMON
26.REQUEST
+5 V
240
240
30.RESET
240
31.POLARITY
240
( / polarity)
Refer to the following User's Manual for application precautions and other information required when using the Digital Indicator:
K3HB-R/P/C Digital Indicator User's Manual (Cat. No. N136)
The manual can be downloaded from the following site in PDF format: OMRON Industrial Web http://www.fa.omron.co.jp
All data "High"
Data
40 ms
16 ms
REQ. (1)
REQ. (2)
REQ. (3)
(1)
DATA
DATA
VALID
Note: Leave 20 ms min. between DATA VALID turning OFF and the REQUEST signal.
SYSMAC Programmable Controller
DC Input Unit
COM
IN
IN
IN
IN
IN
IN
Transistor Output Unit
OUT
OUT
COM
(0 V)
24 VDC
+24 V
Note: The BCD output connector pin number is the D-sub connector pin number when
DC power
supply
the BCD Output Cable (sold separately) is connected. This number differs from
0 V
the pin number for the Digital Indicator narrow pitch connector (manufactured by
Honda Tsushin Kogyo Co., Ltd.).

Continuous Data Output

REQ.
MAX.MIN.
DATA
All data "High"
DATA
VALID
Approx.
30 ms
Measurement data is output every 64 ms while the REQUEST signal
remains ON.
Note: If HOLD is executed when switching between data 1 and data
2, either data 1 or data 2 is output depending on the timing of
the hold signal. The data will not go LOW.
(2)
(See note.)
(See note.)
Display Unit Connection Example
Digital Indicator
Connector pin No. (See note.)
1.COMMON
2.1
3.2
4.4
5.8
23.DATA VALID
24.RUN
25.COMMON
26.REQUEST
+5 V
240
240
30.RESET
240
31.POLARITY
240
( / polarity)
Digital Indicators
Data 1
Data 2
40 ms
40 ms
24 ms
64 ms
64 ms
(3)
(See note.)
10
To 10
1
To 10
2
Short-
circuit
8
8
M7E-01D@N2, 01H@N2
<M7E Digital Display Unit>
K3HB-R/-P/-C
24 ms
8
SEC
25