Monitoring the GRT1-PNT

3-5

Monitoring the GRT1-PNT

Monitoring Features
3-5-1
Communication Unit's Status Flags
62
After network commissioning has been finished and there is communication
between the PROFINET IO Controller Unit and the GRT1-PNT, there are
multiple ways to monitor the status of the GRT1-PNT and its connected
SmartSlice I/O Units.
The monitoring status is available are displayed by the DTMs or can be
accessed from the IO Controller and used within the PLC program.
There are three types of monitoring information
The Communication Unit's Status Flag as part of PROFINET IO Data
The PROFINET IO Communication Status as indicated by the PROFINET
IO Controller
The GRT1-PNT status information using the DTM
The Communication Unit's status or in short COM status flags are allocated as
the first word within the PROFINET IO Data with the PROFINET IO Controller.
These flags can be used to monitor the status of the connection between the
GRT1-PNT and the SmartSlice I/O Units as well as the status of the
SmartSlice I/O Units themselves. The table below defines the individual bits in
the Status word.
/i
Bit
Content
0
SmartSlice I/O Bus
Communication Error Flag
1
Reserved
2
SmartSlice I/O Unit Warning Flag
0: Normal
1: Error detected
3
Reserved
4
SmartSlice I/O Unit Alarm Flag
0: Normal
1: Error detected
5 to 7
Reserved
8
Port 2 Link Status
0 = Link up
1 = Link down
9
Port 1 Link Status
0 = Link up
1 = Link down
10 to 11 Reserved
12
Unit Maintenance Flag
0: Normal
1: Error (monitor value reached)
Description
Monitors the status of SmartSlice I/O
System communication.
---
Indicates a minor SmartSlice I/O Unit
error.
This flag goes ON when there is an error
in any of the connected SmartSlice I/O
Units.
---
Indicates a major SmartSlice I/O Unit
error.
This flag goes ON when there is an error
in any of the connected SmartSlice I/O
Units.
---
Indicates the communication link status
of port 2.
Indicates the communication link status
of port 1.
---
Monitors the Unit's operating time: the
power ON time threshold set with the
Unit power ON time monitor function.
Section 3-5