Page 1
G2RV The World's First Industrial Slim Relay • Large plug-in terminals for reliable connection. • LED indicator and mechanical flag to check operation. • Transparent housing enables checking relay condition. • Slim outline to save space. • Push-in terminals and accessories for easy wiring.
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude) Malfunction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude)
Page 3
Coil ratings Contact ratings Operations G2RV-SL Series SPDT 12 to 48 VDC 250 VAC 6 A (Resistive Load) 6,000 24 to 230 VAC 30 VDC 6 A (Resistive Load) 400 VAC 2 A (Resistive Load) IEC/VDE (EN 61810) Contact form...
G2RV-SL7@@/5@@ AC110 12 ~ 15 ms 22 ~ 30 ms G2RV-SL7@@/5@@ AC230 12 ~ 15 ms 22 ~ 30 ms Accessories ■ PLC Interface (for G2RV-SL700 series only) List of Models Model number Description Connection P2RVC-8-O-F PLC Output Interface for 8x...
Technical data Control line AWG26/0.14 mm , tin-plated copper Diameter cable 10.6 mm (one end splits into 4 sections: A, B, C, D Operating voltage 60 VDC Continuous current per signal wire 0.5 A Max. total current, 4 bytes, each 1.0 A...
P2RV-@@@C-SIM S7/@00 Cables to connect Siemens S7/300 or S7/400 to 4 x P2RVC-8-O-F List of Models Model number Cable length PLC type Configuration P2RV-200C-SIM S7/300 2.0 m Siemens S7/300 4x1 Byte P2RV-250C-SIM S7/300 2.5 m P2RV-300C-SIM S7/300 3.0 m P2RV-500C-SIM S7/300 5.0 m...
■ Plastic Labels for G2RV Sockets Model number Box quantity Color R99-15 for G2RV 1 piece = 1 sheet = 120 labels White ■ Labels (Stickers) for G2RV Sockets Model number Box quantity Color R99-16 for G2RV...
■ Separating Plates Model number Description P2RV-S Provides isolation between adjacent relays to achieve 400 V isolation. Dimensions Note: All units are in millimeters unless otherwise indicated. Complete Unit G2RV-SL700 Input circuit 106.7 max. 70.9 47.2 6.2 max. 26.1 24 V DC...
Page 9
G2RV-SL500 Input circuit 106.7 max. 82.9 69.8 6.2 max. 24.6 24 V DC Terminal Arrangement/ Internal Connections (Top View) 97.4 max. Other Coil Voltage Terminal Arrangement/ Internal Connections (Top View) 88.9 99.2 12 V DC Terminal Arrangement/ Internal Connections Single Relay G2RV-1-S 30.5 max.
■ Tools G2RV-SL700 series: Flat-Blade screwdriver should be used for mounting and / or releasing cables. G2RV-SL500 series: Flat-Blade screwdriver should be used for mounting stranded wires without ferrules and / or releasing cables. Applicable Screwdriver ● Flat-blade, Parallel-tip, 2.5 mm diameter (3.0 mm max.) ●...
Page 11
■ Wiring Use wires of the applicable sizes specified above. The length of the exposed conductor should be 7 mm for a G2RV-SL700 series, 12 mm for a G2RV-SL500 series. G2RV-SL700 7 mm G2RV-SL500 12 mm Fig. 1 Exposed Conductor Length...
• Insert the screwdriver along the hole wall as shown below. Screwdriver ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. J11E-EN-02B In the interest of product improvement, specifications are subject to change without notice.