Communications Specifications - Omron E5ZE-8 D1 B-V2 Datasheet

Multipoint temperature controller
Table of Contents

Advertisement

Dimensions
Enclosure rating
Weight
Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400 C or 750 F max. is not guaranteed. The following measure-
ment accuracy values are applied to the E5ZE.
K and T at –100 C max. and U:
K and T at –100 F max. and U:
R, S, and W at 200 C max., and B at 1,000 C max.:
R, S, and W at 400 F max., and B at 1,800 F max.:
2. The measurement accuracy of the E5ZE used with any thermocouple is 1 C/ F. The thermocouple can be used under the following tem-
perature ranges to increase the measurement accuracy to as high as 0.1 C/ F.
K thermocouple:
T or U thermocouple:
N thermocouple:
J, E, L, or PLII thermocouple: Any temperature
3. Upper limit is 3000.0 C/ F when set from CompoBus/D.

Communications Specifications

Conforming to DeviceNet Communications Protocol
For details, refer to the CompoBus/D (DeviceNet) Operation Manual (W267) and the E5ZE-8 Communication Manual (H114).
Connection method
Baud rate
Communications media
Communications distance
Remote I/O points
Error control
Note: 1. An external terminator must be attached.
2. Indicates the distance between nodes farthest from each other.
3. The maximum network length is 100 m if a thin dedicated cable is applied to the trunk line.
!NOTICE
This product has been tested by ODVA's authorized Independent
Test Lab and found to comply with ODVA Conformance Test Soft-
ware Version A-13.
For the specifications of objects in details, refer to the E5ZE-8 Com-
munication Manual (H114).
DeviceNet Communications Items
Remote I/O communications
Explicit message communications
Note: Items for the OUT side of remote I/O are not included.
With casing: 173.5 x 253 x 65 mm max.
IP00
With casing:1,700 g max.
0.0 C to 1,300.0 C, 0.0 F to 2,300.0 F
0.0 C to 400.0 C, 0.0 F to 700.0 F
400.0 C to 1,300.0 C, 700.0 F to 2,300.0 F
Multi-drop or T-branching (see note 1)
500/250/125 kbps
Dedicated 5-wire cable (with 2 communications wires, 2 power wires, and 1 shield wire)
Baud rate
Maximum network length (see note 2)
500 kbps
100 m max. (see note 3)
250 kbps
250 m max. (see note 3)
125 kbps
500 m max. (see note 3)
IN: 14 / OUT: 9
CRC error and node address duplication check
IN:
PV (process value) (8 points), Alarms 1 and 2 status, AT status, HB alarm status,
HS alarm status, and error status
OUT:
RUN/STOP and SP (set point) (8 points)
All read and write parameters (See note.)
Multipoint Temperature Controller
3 C 1 digit max.
5.4 F 1 digit max.
4 C 1 digit max.
7.2 F 1 digit max.
Branch line length
6 m max.
6 m max.
6 m max.
E5ZE-8@D1@B-V2
Total branch line length
39 m max.
78 m max.
156 m max.
5