Input Ranges; Platinum Resistance Thermometer - Omron E5ZE-8 D1 B-V2 Datasheet

Multipoint temperature controller
Table of Contents

Advertisement

Input Ranges

Thermocouple
Input
K (CA)
J (IC)
(switch
Chromel
Iron vs.
selectable)
vs. alumel
constan-
(see
tan
note 1)
Range
C
–200 to
–100 to
1,300
850
F
–300 to
–100 to
2,300
1500
Setting no.
0
1
Min. setting
1 C or 0.1 C
unit

Platinum Resistance Thermometer

Input
(switch selectable)
Range
C
–100.0 to 500.0
F
–100.0 to 900.0
Setting no.
0
Min. setting unit
1 C or 0.1 C
Characteristics
Measurement accuracy (see note)
Hysteresis
Cooling coefficient
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
Dead band/overlap band
Alarm output setting range
Fuzzy strength
Fuzzy scale 1
Fuzzy scale 2
Set value backup
Set value backup period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
4
Multipoint Temperature Controller
R
S
T (CC)/U
Platinum
Platinum
Copper
vs. Plati-
vs. Plati-
vs. con-
num rhod-
num rhod-
stantan
ium 13%
ium 10%
0 to 1,700
0 to 1,700
–200 to
400
0 to 3,000
0 to 3,000
–300 to
700
2
3
4
Pt 100
JPt 100
(see note 1)
–100.0 to 500.0
–100.0 to 900.0
1
Thermocouple:
( 0.3% of the process value or 2 C, whichever greater) 1 digit max.
( 0.3% of the process value or 3.6 F, whichever greater) 1 digit max.
Platinum resistance thermometer:
( 0.3% of the process value or 0.8 C, whichever greater) 1 digit max.
( 0.3% of the process value or 1.5 F, whichever greater) 1 digit max.
0.0 to 99.9 C/ F for ON/OFF control only (in units of 0.1 C/ F)
0.0 to 10.0 (in units of 0.1)
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
Cooling side: Cooling coefficient
0 to 3,999 s (in units of 1 s) (for both heating and cooling)
0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Heating side:
1 to 99 s (in units of 1 s)
Cooling side:
1 to 99 s (in units of 1 s)
200 ms for 8 control points
–999 to 999 C/ F (in units of 1 C/ F)
–999 to 9999 C/ F, 0 to 9999 C/ F (upper- and lower-limit alarm) (in units of 1 C/ F)
–999.9 to 9999.9 C/ F, 0.0 to 9999.9 C/ F (upper- and lower-limit alarm) (in units of 0.1 C/ F) (see note
3)
0% to 99% (in units of 1%)
0.2 to 999.9 C/ F (in units of 0.1 C/ F)
0.02 to 99.99 C/s or F/s (in units of 0.01 C/s or F/s)
Lithium battery
10 years min. provided that the ambient temperature is within the room temperature
20 M
min. between the FG terminal and all analog input terminals (at 500 VDC)
A leakage current of 1 mA AC max. with 500 VAC for 1 minutes between the FG terminal and all analog
input terminals
Malfunction: 10 to 55 Hz, 15 m/s
Destruction: 10 to 55 Hz, 20 m/s
Malfunction: 150 m/s
Destruction: 200 m/s
Operating:
0 to 55 C (with no icing or condensation)
Storage:
–25 to 65 C (with no icing or condensation)
Operating:
35% to 85%
Storage:
35% to 95%
E5ZE-8@D1@B-V2
E (CRC)
B
Chromel
Platinum
Nichrosil
vs. con-
rhodium
stantan
30% vs.
platinum
rhodium
6%
0 to 600
100 to
0 to 1,300
1,800
0 to 1100
300 to
0 to 2,300
3,000
5
6
7
Note: 1. A temperature range is factory-set to a range of –200 to
1,300 C (for K(CA)) or –100.0 to 500.0 C (for Pt 100).
2. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tung-
sten rhenium 26).
Proportional band
2
for 8 min each in X, Y, and Z directions
2
for 8 min each in X, Y, and Z directions
2
, 3 times each in 6 directions
2
, 3 times each in 6 directions
N
L
U
Iron vs.
Copper
vs. nisil
constan-
vs. con-
tan
stantan
–100 to
–200 to
850
400
–100 to
–300 to
1,500
700
8
9
W
PL-II
(see
(Platinum)
note 2)
0 to 2,300
0 to 1,300
32 to 4,100 0 to 2,300
A
B