Fault Detection

When the Non-contact Door Switch Controller detects a fault, the ERR indicator and/or other indicators light up or flash to inform the user about
the fault.
Check and take necessary measures referring to the following table, and then re-supply power to the Non-contact Door Switch Controller.
(G9SX-NS202-@/NSA222-T03-@)
ERR
Other
indicator
indicator
Fault due to
electromagnetic
---
disturbance or of internal
Flashes
circuits.
Fault involved with safety
input 1
T1 flashes
Fault involved with safety
input 2
T2 flashes
Fault involved with
Non-contact Door Switch
NS
input
flashes
Fault involved with
feedback/reset inputs
FB
flashes
Fault in Expansion Unit
Lights
Fault involved with
instantaneous safety
outputs, logical AND
EI flashes
connection outputs, or
auxiliary monitor output
Fault involved with
OFF-delayed safety
ED
outputs
flashes
Fault
Expected causes of the fault
1. Excessive electromagnetic
disturbance
2. Failure of the internal circuit
1. Error in the wiring of safety input 1
2. Incorrect setting of cross fault
detection input
3. Failure of the circuit of safety input 1
1. Error in the wiring of safety input 2
2. Incorrect setting of cross fault
detection input
3. Failure of the circuit of safety input 2
1. Error in the wiring of Non-contact
Door Switch input
2. Error in the wiring of Non-contact
Door Switch inputs in series
connections.
3. Failure of the internal circuits of
Non-contact Door Switch inputs
4. Failure of the Non-contact Door
Switch
1. Error in the wiring of feedback/reset
input.
2. Failure of the circuit of feedback/
reset input
1. Improper feedback signals from
Expansion Unit
2. Abnormal supply voltage to
Expansion Unit
3. Failure of the circuit of safety relay
contact outputs
1. Error in the wiring of instantaneous
safety outputs
2. Failure of the circuit of instantaneous
safety outputs
3. Error in the wiring of the logical AND
connection output
4. Failure of the circuit of the logical
AND connection output
5. Error in the wiring of the auxiliary
monitor output
6. Impermissible high ambient
temperature
1. Error in the wiring of OFF-delayed
safety relay contact outputs
2. Incorrect set values for OFF-delay
time
3. Failure of the circuit of OFF-delayed
safety relay contact outputs
4. Impermissible high ambient
temperature
D40A/G9SX-NS
Check points and measures to take
1. Check the disturbance level around the G9SX
and the related system.
2. Replace with a new product.
1. Check the wiring to T11 and T12.
2. Check the wiring to Y1.
3. Replace with a new product.
1. Check the wiring to T21 and T22.
2. Check the wiring to Y1.
3. Replace with a new product.
1. Check the wiring to D1 and D2.
2. Check the wiring to the D40A.
3. Replace with a new product.
4. Replace with a new D40A.
1. Check the wiring to T31, T32 and T33.
2. Replace with a new product.
1. Check the connecting cable of Expansion Unit
and the connection of the termination socket.
2. Check the supply voltage to Expansion Unit.
Note: Make sure that all Expansion Units' PWR
indicators are lit.
3. Replace with a new product.
1. Check the wiring to S14 and S24.
2. Replace with a new product.
3. Check the wiring to L1.
4. Replace with a new product.
5. Check the wiring to X1.
6. Check the ambient temperature and spacing
around the G9SX.
1. Check the wiring to S44 and S54.
2. Check the settings of the OFF-delay time setting
switch.
3. Replace with a new product.
4. Check the ambient temperature and spacing
around the G9SX.
20