Ratings (Non-contact Door Switch Controllers)

Power input

Item
Rated supply voltage
Operating voltage range
Rated power consumption *
* Power consumption of loads not included.
Inputs
Item
Safety input *1
Feedback/reset input
*1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Door Switch.
*2. Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item
Instantaneous safety output *1
OFF-delayed safety output *1
Auxiliary output
*1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
ON
OFF
360 μs max.
*2. The following derating is required when Units are mounted side-by-side.
G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A max. load current

Expansion Unit

Item
Model
Rated load
Rated carry current
Maximum switching voltage 250 VAC, 125 VDC
Model
G9SX-NS202-@
24 V DC
−15% to 10% of rated supply voltage
3 W max.
Model
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kΩ *2
Model
P channel MOS FET transistor output
Load current: 0.8 A DC max. *2
PNP transistor output
Load current: 100 mA max.
Approx.100 ms
G9SX-EX-@
250 VAC, 3 A/30 VDC, 3 A (resistive load)
3 A
G9SX-NSA222-T03-@
4 W max.
G9SX-NS202-@/G9SX-NSA222-T03-@
G9SX-NS202-@/G9SX-NSA222-T03-@
D40A/G9SX-NS
G9SX-EX-@
2 W max.