PART 3: CX-Server Runtime
CHAPTER 3 – Communications
Setting Procedures
Specifying the PLC to Connect to via the PT
The procedures for connecting the CX-Programmer to a PLC via an NS-series PT are given below. Be sure that
normal communications are possible between the PT and PLC before performing any of these procedures.
Downloading Ladder Programs or Other Data to a PLC with an Ethernet Connection between
the Computer and PT and a 1:N NT Link Serial Connection between the PT and PLC
Downloading Ladder Programs or Other Data to a PLC with an Ethernet Connection between
the Computer and PT and a Controller Link Connection between the PT and PLC
CX-Server Runtime_Page 34
Note 3:
If the CP1W-CIF41 is used, the PLC containing it cannot be used as a gateway PLC to cross
network layers.
Note 4:
Use FINS/UDP for communications with the NS-series PT when using an EtherNet/IP Unit or
built-in EtherNet/IP port on the CPU Unit.
Note 5:
An Option Board can be mounted only to a CPU Unit with 30 or 40 Points.
The CP1E-E@@D@-A cannot be connected via an NS-series PT because it has no built-in RS-
232C port and an Option Board cannot be mounted.
CX-Programmer
Ethernet
1. Start the CX-Programmer.
2. Set the network type in the Change PLC Dialog Box to Ethernet and click the Set Button.
3. Input the IP address of the PT to connect to on the Driver Tab Page of the Network Settings
Dialog Box.
4. Click the Network Tab and set the following items.
Item
FINS Source Address
FINS Destination Address
Node
Note:
Data cannot be transferred normally if any value other than 1 is set.
5. After completing the settings, connect online and transfer the ladder programs or other data.
CX-Programmer
Ethernet
1. Start the CX-Programmer.
2. Set the network type in the Change PLC Dialog Box to Ethernet and click the Set Button.
3. Input the IP address of the PT to connect to on the Driver Tab Page of the Network Settings
Dialog Box.
NS-series PT
Serial
Input the local network address of the PT.
Input 111 if the PLC is connected to serial port A on the PT.
Input 112 if the PLC is connected to serial port B on the PT.
Input 1 (fixed). (See note.)
NS-series PT
Controller
Link
PLC
Description
PLC
OMRON
Revision 2.0