Interrupt Functions

6-1
Interrupt Functions
6-1-1

Overview of CP1L Interrupt Functions

Types of Interrupt
Functions
Input Interrupts (Direct
Mode)
Input Interrupts (Counter
Mode)
Scheduled Interrupts
High-speed Counter
Interrupts
Note
Creating an Interrupt
Task Program
1,2,3...
338
The CP1L CPU Unit's processing is normally cyclical (overseeing processing
program execution
tasks executed in the program execution stage of the cycle. The interrupt
functions can be used to temporarily interrupt this cyclic processing and exe-
cute a particular program when a predefined condition occurs.
When one of the CPU Unit's built-in inputs goes from OFF to ON (or ON to
OFF), the corresponding interrupt task is executed. Interrupt tasks 140 to 145
are allocated to the 8 input terminals used for the input interrupts.
This function counts input pulses at one of the CPU Unit's built-in inputs and
executes the corresponding interrupt task when the count reaches the SV.
The maximum input response frequency for input interrupts (in counter mode)
is 5 kHz.
This function executes an interrupt task at a fixed time interval measured by
the CPU Unit's built-in timer. The time interval units can be set to 10 ms, 1 ms,
or 0.1 ms. The minimum timer SV is 0.5 ms.
Interrupt task 2 is allocated to scheduled interrupt.
This function counts input pulses with the CPU Unit's built-in high-speed
counter and executes an interrupt task when the count reaches the preset
value or falls within a preset range (target-value or zone comparison). An
interrupt task between 0 and 255 can be allocated with an instruction.
Refer to 5-1 High-speed Counters for details on high-speed counters.
Power OFF interrupts cannot be used with CP1L CPU Units.
1. Right-click NewPLC1 [CP1L] Offline in the project workspace and select
Insert Program from the pop-up menu. A new program called
NewProgram2 (unassigned) will be inserted in the project workspace.
I/O refreshing
peripheral servicing), with cyclic