Reset Methods - Omron CP1L - 12-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

High-speed Counters

Reset Methods

Phase-Z Signal + Software
Reset
Software Reset
Restrictions
• There are no negative values in ring mode.
• If the max. ring count is set to 0 in the PLC Setup, the counter will operate
with a max. ring count of FFFFFFFF hex.
The high-speed counter's PV is reset when the phase-Z signal (reset input)
goes from OFF to ON while the corresponding High-speed Counter Reset Bit
is ON.
The CPU Unit recognizes the ON status of the High-speed Counter Reset Bit
only at the beginning of the PLC cycle during the overseeing processes. Con-
sequently, when the Reset Bit is turned ON in the ladder program, the phase-
Z signal does not become effective until the next PLC cycle.
Phase-Z
Reset Bit
PV not
reset
The high-speed counter's PV is reset when the corresponding High-speed
Counter Reset Bit goes from OFF to ON.
The CPU Unit recognizes the OFF-to-ON transition of the High-speed
Counter Reset Bit only at the beginning of the PLC cycle during the oversee-
ing processes. Reset processing is performed at the same time. The OFF-to-
ON transition will not be recognized if the Reset Bit goes OFF again within the
same cycle.
Reset Bit
Note The comparison operation can be set to stop or continue when a high-speed
counter is reset. This enables applications where the comparison operation
can be restarted from a counter PV of 0 when the counter is reset.
One cycle
PV
PV
reset
reset
One cycle
PV
PV not
reset
reset
PV
PV not
reset
reset
PV not
PV not
reset
reset
Section 5-1
PV
reset
161

Advertisement

Table of Contents
loading

Table of Contents