TSC 80e SPECIFICATIONS

POWER SUPPLY:
- 120VAC nominal (+10% -30%)
- 50/60Hz
- 6VA nominal (no external load connected)
VOLTAGE SENSING:
- Direct 120-600VAC nominal, single or 3 phase
- 50/60Hz
- +/- 1.0% accuracy of setting @ 25° C
OPERATING TEMPERATURE:
- 15° C to +50° C
OUTPUT CONTACTS (Form C, 10A,120/250VAC resistive)
- Engine Start
- Programmable Output Contact #1
- Programmable Output Contact #2
- Programmable Output Contact #3
- Programmable Output Contact #4
- Programmable Output Contact #5
OUTPUT SIGNALS (120VAC resistive load)
- Transfer to utility 10A
- Transfer to generator 10A