Specific Conditions Of Use ("X" Identification); Installation - Vega VEGAPULS 6X Series Safety Instruction

Nonincendive four-wire modbus
Hide thumbs Also See for VEGAPULS 6X Series:
Table of Contents

Advertisement

4
Specific conditions of use ("X" identification)
The following list describes the special operating conditions of VEGAPULS 6X.
In the application the following applies to the radar sensors VEGAPULS 6X in the versions with
Aluminium/Titanium:
– Installation must be carried out in such a way that the generation of sparks as a result of impact
and friction processes between Aluminium/Titanium and steel is excluded. This excludes stain-
less steel without rust particles.
Certain components of the radar sensor VEGAPULS 6X can charge electrostatically. These
include: Plastic housings, non-grounded metal parts, plastic antennas. For details, refer to chap-
ter "Electrostatic charge (ESD)" of these safety instructions.
To avoid the risk of electrostatic charging of metal parts, the VEGAPULS 6X must be connected
to the potential equalization (transition resistance ≤ 1 MΩ).
All parts of VEGAPULS 6X in contact with the medium must only be used in such a medium
against which the materials are sufficiently resistant.
VEGAPULS 6X with rinsing connection: It must be ensured that the IP67 degree of protection is
provided at the connection to the reflux valve when used as zone 0/1 (EPL Da/Db) instruments.
After removing the reflux valve or the rinsing facility on the refölux valve, the opening must be
closed with a suitable screw plug so that the IP67 degree of protection is maintained.
VEGAPULS 6X with swivelling holder: It must be ensured that the IP67 degree of protection is
maintained when operating as zone 0/1 (EPL Da/Db) instrument after aligning the antenna using
the swivelling holder and after screwing on the tension flange.
Ambient temperature
– You can find the details in chapter "Thermal data" of these safety instructions.
5

Installation

The installation of the device must only be carried out by qualified personel.
The staff must be trained in explosion protection and familiar with the relevant valid regulations.
Make sure when working on the instrument that there is no explosive atmosphere present. The
supply circuits should be voltage-free, if possible.
Install the instrument in accordance with the manufacturer specification and the applicable
national regulations, e.g. planning and installation in accordance with IEC/EN 60079-14.
The devices must be integrated into the local potential equalization.
If grounding of the cable screening is necessary, this must be carried out acc. to the valid stand-
ards and regulations, e.g. acc. to IEC/EN 60079-14.
Close the housing lid (s) up to the stop before starting operating, to ensure the IP protection rat-
ing specified on the type label.
For device category 2 the following process pressures are applicable depending on the antenna
version:
Plastic horn antenna, with inspection window
Thread with integrated horn antenna, with inspection window
Flange with encapsulated antenna system, with inspection window -1 ... +25 bar
Flange with lens antenna, with inspection window
Hygienic version with thread
Hygienic version with tension flange or compression nut
Horn antenna
VEGAPULS 6X
Process pressure
Compression flange -1 ... +2 bar
Adapter flange -1 ... +1 bar
-1 ... +40 bar
-1 ... +3 bar
-1 ... +25 bar
-1 ... +16 bar
-1 ... +100 bar