(4) If the inverter experiences a Fault it will enter Fault mode and display the current or most recent
faults.
The inverter will disconnect from the power grid and turn into fault mode when the inverter or power grid
fails. Check the specific cause in "Troubleshooting Table" (Section 8) according to the fault message
displayed on the LCD and eliminate the fault referred to in the instructions. The fault information of the
most recent / currently present fault will be shown on the LCD when the inverter is in fault mode.

6. Commissioning

Before powering up the PV system it is important to check the installation for any hazards that may be present.

Commissioning Checklist

Follow the Checklist: For your safety, please follow the guidelines below during the startup of your inverters.
Mechanical Installation
 Ensure that the mounting bracket is secure and all the screws have been tightened to the specified torque
values. (Please refer to Section 4.2.5.1)
 Confirm all knockouts are sealed and conduits are securely attached to the inverter creating a water-tight
seal.
 Confirm that all conduit entries into the inverter have been sealed with duct sealant to prevent
condensation from entering into the Wiring Box.
Electrical Connections
 Make sure all conductors are landed on the correct terminals and properly labeled.
 Ensure that no sharp edges from cable ties exist. Appropriate cable management is the key to avoiding
physical damage.
 Make sure all connections are tightened to torque specifications as per Section 4.3 Electrical Installation.
 The polarity of DC input cables should be correct and the DC Switch should be in the "OFF" position.
DOCR-071086-C (04/12/2024)
History Record
Current Error
Running Record
Fault Record
Figure 5-6 History Record Interface