Wiring Specifications - Linear HSLG Series Installation Manual

Slide gate operator
Hide thumbs Also See for HSLG Series:
Table of Contents

Advertisement

Wiring Specifications

Refer to the following steps for details on power and accessory wiring
for the operator.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.
USE COPPER WIRE ONLY!
AC Power Wiring
1. Find the listing on this page corresponding to the model, voltage
and horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the
operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE. These calculations have been based on standard 115 V
and 230 V supplies with a 10% drop allowable. If your supply is
under the standard rating, the runs listed may be longer than what
your application will handle, and you should not run wire too near
the maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not
supplied) may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code,
Article 430 and have been carefully determined based on motor
inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground
wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience
with occasional use or low power consumption devices only. If you
choose to run dedicated equipment from these devices, it will
decrease the distance for maximum length and the charts will no
longer be accurate.
DC Control and Accessory Wiring
1. All control devices are now 24 VDC, which can be run up to
2000 feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring.
Running them together may cause interference and faulty signals
in some accessories.
3. A three-wire shielded conductor cable is required to connect two
operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,
per foot). See Page 23 for details of this connection. Note: The
shield wire should be connected in both the operators.
HSLG Slide Gate Operator Installation Guide
www.LinearGateOpeners.com | (888) 378-1053 | Sales@LinearGateOpeners.com
MODEL HSLG SINGLE PHASE POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
115 VOLTS
1/2-HP
1430
115 VOLTS
3/4-HP
1140
115 VOLTS
1-HP
1026
1200
208 VOLTS
1924
1/2-HP
3060
4864
208 VOLTS
1526
3/4-HP
2424
3856
208 VOLTS
1374
1-HP
2184
3476
894
1422
230 VOLTS
2264
1/2-HP
3600
5724
710
1128
230 VOLTS
1796
3/4-HP
2852
4538
640
1016
230 VOLTS
1616
1-HP
2570
4090
MODEL HSLG THREE PHASE POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
1142
208 VOLTS
1816
1/2-HP
2890
208 VOLTS
1464
3/4-HP
2330
208 VOLTS
1136
1-HP
1804
1344
230 VOLTS
2137
1/2-HP
3400
1084
230 VOLTS
1723
3/4-HP
2741
230 VOLTS
1336
1-HP
2124
3841
460 VOLTS
6106
1/2-HP
9712
3279
460 VOLTS
5212
3/4-HP
8291
2689
460 VOLTS
4274
1-HP
6798
- 2 -
DUAL
222
111
354
177
566
283
900
450
715
178
89
282
141
450
255
716
358
570
160
80
254
127
406
203
646
323
513
760
380
600
962
1830
2432
604
302
958
478
763
1212
1928
544
272
864
432
686
1092
1738
447
711
1132
1800
2862
355
564
898
1426
2269
320
508
808
1285
2045
DUAL
571
908
1445
920
460
732
1165
714
357
568
902
672
1069
1700
542
862
1371
840
420
668
1062
1921
3053
4856
1640
2606
4146
1345
2437
3399
WIRE GAUGE
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
12
10
8
6
4
WIRE GAUGE
12
10
8
12
10
8
12
10
8
12
10
8
12
10
8
12
10
8
12
10
8
12
10
8
12
10
8
P1220 X14