Wiring Specifi cations
Refer to the following steps for details on power and
accessory wiring for the operator.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.
USE COPPER WIRE ONLY!

AC Power Wiring

1. Find the listing on this page corresponding to the model, voltage and
horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the
operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE. These calculations have been based on standard 115 V
and 230 V supplies with a 10% drop allowable. If your supply is under
the standard rating, the runs listed may be longer than what your
application will handle, and you should not run wire too near the
maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not
supplied) may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code,
Article 430 and have been carefully determined based on motor
inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground
wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience
with occasional use or low power consumption devices only. If
you choose to run dedicated equipment from these devices, it will
decrease the distance for maximum length and the charts will no
longer be accurate.

DC Control and Accessory Wiring

1. All control devices are now 24 VDC, which can be run up to 2000
feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring.
Running them together may cause interference and faulty signals in
some accessories.
3. A three-wire shielded conductor cable is required to connect two
operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,
per foot). See Page 19 for details of this connection. Note: The shield
wire should be connected in both the operators.
SG • SG-D Barrier Gate Operator Installation Guide
MODEL SG POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
115 VOLTS
1/2-HP
230 VOLTS
1/2-HP
MODEL SG-D POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
115 VOLTS
1/2-HP
- 2 -
DUAL
222
111
354
177
566
283
900
450
894
447
1422
711
2264
1132
3600
1800
DUAL
222
111
354
177
566
283
900
450
P1277 Revision X2 8-11-2011
WIRE GAUGE
12
10
8
6
12
10
8
6
WIRE GAUGE
12
10
8
6