Mounting The Outdoor Unit; About Mounting The Outdoor Unit; Precautions When Mounting The Outdoor Unit; To Provide The Installation Structure - Daikin RXYSA4A7V1B Installer And User Manual

System air conditioner
Table of Contents

Advertisement

17.3 Mounting the outdoor unit

17.3.1 About mounting the outdoor unit

17.3.2 Precautions when mounting the outdoor unit

17.3.3 To provide the installation structure

RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1A – 2020.07
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1
Providing the installation structure.
2
Installing the outdoor unit.
3
Providing drainage.
4
Preventing the unit from falling over.
INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautions
Preparation
Check the strength and level of the installation ground so that the unit will not
cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance with the
foundation drawing.
Prepare 4 sets of anchor bolts, nuts and washers (field supply) as follows:
(mm)
a
Make sure not to cover the drain holes of the bottom plate of the unit.
INFORMATION
The recommended height of the upper protruding part of the bolts is 20 mm.
17
Unit installation
|
4× M12
a
Installer and user reference guide
73

Advertisement

Table of Contents
loading

Table of Contents