16
|
Unit installation

16.2 Mounting the indoor unit

16.2.1 Guidelines when installing the indoor unit

Installer and user reference guide
46
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will NOT occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3  m or more to avoid
electromagnetic interference of other equipment and use conduit tubes for power
and transmission lines.
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone and the location is selected according the
applicable legislation.
Drainage. Make sure condensation water can be evacuated properly.
Paper pattern for installation (accessory). Use the paper pattern when selecting
the installation location. It contains the dimensions of the unit and locations of
suspension bolts and piping connection side.
Spacing. Mind the following requirements:
a
A:
A:
A:
1500
1500
A Minimum distance to the wall
Minimum: 1.5 m on the air outlet side and 150 mm on the other sides
B Minimum and maximum distance to the floor
Minimum: 2.5 m to avoid accidental touching.
Maximum: 3.5 m. See
a Air outlet
b Air inlet
c Indoor unit
d Floor
INFORMATION
Some options may require additional service space. Sees the installation manual of
the used option before installation.
INFORMATION
Optional equipment. When installing optional equipment, also read the installation
manual of the optional equipment. Depending on the field conditions, it might be
easier to install the optional equipment first.
b
A:
150
150
c
d
"20.1 Field
setting" [
A:
150
(mm)
4
 67].