16
|
Unit installation
To mount the indoor unit
Installer and user reference guide
48
Side view
a
b
a Suspension bolt
b Ceiling
NOTICE
Make sure the decoration panel overlaps the ceiling opening by at least 20 mm. The
distance between the indoor unit and the ceiling opening must be ≤35  mm; if it is
more, install additional ceiling material or repair the ceiling.
a
b
≤35
d:
c:
≥20
490~510
a Frame
b Additional ceiling material
c Ceiling opening
d Ceiling overlapping part of the decorative panel
1 Handle the unit only by the hanger brackets.
2 Temporarily hang the unit on the 2 suspension bolts on one side.
3 Insert the remaining 2 suspension bolts into the hanger bracket and fix it
securely with the bottom washer and nut.
4 Make sure that the unit is level.
a Level
(mm)
≤35
d:
≥20
(mm)
a
FXKQ-A
VRV system air conditioner