Daikin FXKQ20AMVEB User Reference Manual page 70

Vrv system air conditioner
Hide thumbs Also See for FXKQ20AMVEB:
Table of Contents

Advertisement

20
|
Configuration
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
: Default
Installer and user reference guide
70
Wiring requirements
Wiring size
Wiring length
External contact specification
This setting must correspond with the needs of the user.
If you want to set...
Forced OFF
ON/OFF Operation
Emergency (recommended for alarm operation)
Forced OFF - multi tenant
Interlocking setting A
Interlocking setting B
Setting: Mold proof prevention operation
NOTICE
When the function is disabled, mould and odour may form inside the indoor unit.
This setting must correspond with the needs of the user. It determines the fan
operation time after the unit is turned off by the user interface during cooling
mode.
If you want to set the fan operation time after
the unit is turned off to...
Disabled
30 minutes
60 minutes
2
0.75~1.25 mm
Maximum 100 m
Contact that can make and break the
min. load of DC15 V · 1 mA
Then
M
12 (22)
Then
M
14 (24)
(1)
SW
1
01
02
03
04
05
06
(1)
SW
10
01
02
03
FXKQ-A
VRV system air conditioner
4P747548-1 – 2023.11