V8 VRF Indoor Units
6.1.25 C76 - Abnormal communication between the main wired controller and secondary wired controller
Note: The error code C51 can be triggered either at the IDU side or at the wired controller side.
Error display
The faulty IDU and other IDUs of the same system: operate normally. The wired controller does not work.
Error impact
ODU of the same system: operate normally.
Error trigger
If the secondary wired controller has not received any reply from the main wired controller for 1 min
Error recovery
Automatic recovery
Possible cause
Troubleshooting
72
Digital display
The secondary wired controller is damaged.
Communication cables are loose or the communication port is faulty.
Communication cables have short-circuited or been cut off.
C76
Display position (secondary wired controller)
The error code "C76" is displayed only on the secondary wired
controller
Cause 1: The co mmuni cation
cable between th e seconda ry
wired controller and the ma in
wired controller has become
disconnected or sho rt ci rcu ited
Cause 2: The co mmuni cation
cable between th e seconda ry
wired controller and the ma in
wired controller has become
loose or is conne cted to a wrong
port
Cause 3: The se con dary wired
controller is d ama ged
Replace th e
commu nicatio n cable an d
prop erly conn ect the
cable
Pro perly conn ect the
cables and ensure th ey
are conne cted to the right
ports
Replace th e seconda ry
wired controller