Midea V8 VRF Series Service Manual page 24

Commercial air conditioners
Table of Contents

Advertisement

Table 2.2: Indoor unit Parameter Settings(continues)
Parameter
Parameter Name
Code
Setting temperature
N51
adjustment interval when
unattended
Setting maximum
N52
temperature adjustment
when unattended
Stop delay when
N53
unattended
Midea ETA function
N54
setting
Energy rating of cooling
N55
Midea ETA
Energy rating of heating
N56
Midea ETA
On-site fan speed
N57
adjustment factor
Initial static pressure
N58
detection
Filter ending - initial static
N59
pressure setting
Ambient temperature
N60
when preheating is
turned on
N61
Reserved
N62
Reserved
N63
Reserved
Parameter
Default
Range
Value
00/01/02/03/04/
01
05
00/01/02/03
01
00/01/02/03/04/
01
05
01
00/01
00/01/02
00
00/01/02
00
00/01/02/03/04/
00
05/06
00/01
00
00/01/.../19
00
00/01/02
02
V8 VRF Indoor Units
Remarks
00: 15 min
01: 30 min
02: 45 min
03: 60 min
04: 90 min
05: 120 min
00: 1°C
01: 2°C
02: 3°C
03: 4°C
00: 15 min
01: 30 min
02: 45 min
03: 60 min
04: 90 min
05: 120 min
00: Off
01: On
00: Level 1
01: Level 2
02: Level 3
00: Level 1
01: Level 2
02: Level 3
00: 1
01: 1.1
02: 1.05
03: 1.15
04: 0.95
05: 0.9
06: 0.85
00: Not reset
01: Reset
00-10Pa/ 01-20Pa/
02~19-30Pa ~200Pa
00: 5°C
01: 0°C
02: (-5)°C
--
--
--
23