Midea V8 VRF Series Service Manual page 20

Commercial air conditioners
Table of Contents

Advertisement

Table 2.2: Indoor unit Parameter Settings
Parameter
Parameter Name
Code
N00
Static pressure of IDU
Power failure memory
N01
function setting for the
IDU
IDU up/down swing
N02
setting
IDU left/right swing
N03
setting
Whether the display
N04
board of IDU receives
remote control signals
N05
Buzzer of the IDU rings
Light (display panel)
N06
setting
N07
Temperature unit
Mode changeover time
N08
interval in the auto mode
(min)
Set outdoor temperature
N11
value when auxiliary
heater is on
Indoor temperature when
N12
auxiliary heater is on
T1 temperature
N13
difference when auxiliary
heater is on
T1 temperature
N14
difference when auxiliary
heater is off
Parameter
Default
Range
Value
IDU static
pressure level:
00/01/02/03/
02
04/05/06/07/08/
09/~/19
00/01
01
00/01/02/03/04
01
00/01
01
00/01
00
00/01/02
02
00/01
01
00/01
00
00/01/02/03
00
-25°C to 0°C
0°C
10°C to 30°C
24°C
0-7
4
0-10
6
V8 VRF Indoor Units
Remarks
The IDU sets the selected corresponding static pressure (VRF
unit: main board DIP of IDU; other models: reserved)
00: None
01: Available
00: None
01: Available 02/03: Reserved
04: Q4/Q4C four air vents
Note: The IDU can automatically identify up/down swing, so
this function is invalid
00: None
01: Available
Note: The IDU can automatically identify up/down swing, so
this function is invalid
00: Yes
01: No
00: No
01: Yes
02: remote controller only
00: Off
01: On
00: Celsius
01: Fahrenheit
00: 15min
01: 30min
02: 60min
03: 90min
Note: Accuracy is 1°C.
(Accuracy is 1°C)
0-7 indicates 0 - 7°C (Accuracy is 1°C)
0-10 indicates -4 - 6°C (Accuracy is 1°C)
19