Midea V8 VRF Series Service Manual page 23

Commercial air conditioners
Table of Contents

Advertisement

V8 VRF Indoor Units
Table 2.2: Indoor unit Parameter Settings(continues)
Parameter
Parameter Name
Code
Long-distance on/off
N38
function setting
Delay time setting (Using
N39
long-distance on/off port
to turn off the IDU)
Long-distance alarm
N40
function setting
Faster cooling mode
N41
setting
N42
Sterilization function
N43
Sterilization setting
N44
Silent mode setting
N45
ECO
Drying time at
N46
self-cleaning
Mildew-proof fan
operation duration
N47
(power off in cooling/dry
mode, except power off
due to faults)
N48
Dirt proof for ceiling
N49
Condensation proof
N50
Human Detect Sensor
22
Parameter
Default
Range
Value
00/01
00
00/01/.../06
00
00/01
00
00
00/01
00/01
00
00/01/02
00
00/01
00
00/01
01
0/1/2/3
0
00/01/02/03
00
00/01
00
00/01
00
00/01/02
00
Remarks
00: Turn off the IDU when closed
01: Turn off the IDU when open
Note: When turn off the IDU by long-distance on/off port,
the wired controller will display "d6"
00 - No delay
01 - 1min delay
02 - 2min
03- 3min
04- 4min
05- 5min
06- 10min
00: Alarm when closed
01: Alarm when open
00: Off
01: On
00: No sterilization function (default)
01: Plasma disinfection
00: Auto on
01: Forced on
02: Forced off
00: Off
01: On
00: Off
01: On
0: 10 min
1: 20 min
2: 30 min
3: 40 min
00 - Invalid (default)
01 - 60s
02 - 90s
03 - 120s
00: Invalid
01: Valid
00: Invalid
01: Valid
00: Invalid
01: Used to adjust the set temperature when
unattended
02: Used to turn off the unit when unattended