Midea V8 VRF Series Service Manual page 14

Commercial air conditioners
Table of Contents

Advertisement

Table 1.7: Medium Static Pressure Duct main PCB ports (continued)
Label in
Code
Content
Figure 1.4
7
CN81
T2 Temperature sensor connection
8
CN82
T1 Ambient Temperature sensor connection
9
CN83
T2B Temperature sensor connection
10
CN-A
Sterilization module port
11
CN30
Display Panel connection
12
CN35
Humidity sensor connection
13
CN5
Water level port
14
CN190
Drainage pump port
15
CN18
Communication Switch Board,
16
CN16
Reserved
17
CN25
Program burning port(indoor unit)
CN8
18
EEV drive port
19
CN55
Remote control ON/OFF port
X1 X2 communication port(with wire controller);
CN6(X1X
20
2,PQE)
P Q communication port(with ODU by RS-485)
CN2(D1D
21
D1 D2 communication port(with Central controller)
2)
CN10(M1
22
M1 M2 communication port(with ODU by HyperLink)
M2)
23
CN99
After-sale Kit communication port
Notes:
1.
Standard: The model has this function, the customers can connect corresponding device through this port, such as water pump and hotel key card etc.
Customized: This function needs to be customized before leaving the factory.
Reserved: This port can not be used.
2.
When repairing, PQ connects after-sales tooling
3.
PQ and M1M2 communication ports both are used for indoor and outdoor communication, and only one of them can be used at a time. Meanwhile, be
sure to connect the same communication ports (PQ to PQ; M1M2 to M1M2) in case of damage of the main control board.
4.
D1D2 communication ports are used for group control communication. When connecting the group controller, the D1D2 port of the indoor units that are
to be group controlled must be connected in daisy chain, and the group controller must be connected to the X1X2 port of one o f the indoor units in the
group control, and set to group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
5.
Refer to Table 1.2 for voltage test instructions of some ports.
V8 VRF Indoor Units
Port voltage
Note
3.3V DC
Standard
3.3V DC
Standard
3.3V DC
Standard
12V DC
Customized
[5]
12V DC
Standard
[5]
3.3V DC
Customized
[5]
3.3V DC
Standard
[5]
12V DC
Standard
[5]
5V/12V DC
Customized
12V DC
/
[5]
3.3V DC
Standard
Standard
12V DC
[5]
Connect pin 2 and 3,
The IDU will be
Standard
forced to shut down
X1 X2:18V DC ;
P,E or Q,E:
Standard
2.5-2.7V DC
D1,E or D2,E
Standard
2.5 - 2.7V DC
24V DC
Standard
[5]
12V DC
Standard
13