Use a crimp terminal as necessary.
When using the crimp terminal, make sure that the stranded wire do not come out of the terminal.
NOTE
• Crimp terminals commercially available (as of April 2023. The product may be changed without notice.)
Wire gauge
Terminal
2
screw size
(mm
)
0.3
M2
0.5
2.
Loosen the terminal screw and insert the cable into the terminal.
Screw size
Tightening torque
M2
0.22 N•m to 0.25 N•m
NOTE
• The wiring length should be 30 m at the maximum.
• Under-tightening may cause cable disconnection or malfunction. Over-tightening may cause a short circuit or malfunction
due to damage to the screw or option unit.
• When wiring the RS-485 terminals on the inverter with the plug-in options installed, be careful not to let RS-485 cables touch
the option circuit boards and the inverter circuit board. This is to prevent a malfunction due to electromagnetic noises.
Damaged
Crumpled tip
Ferrule part No.
With insulation sleeve
AI 0,34-6TQ
Al 0,5-6WH
Wire gauge
2
2
0.3 mm
to 0.75 mm
Unstranded
wires
Wires are not inserted
into the sleeve
Without insulation sleeve
A 0,34-7
A 0,5-6
Small flathead screwdriver
(Tip thickness: 0.4 mm/tip width: 2.5 mm)
INSTALLATION AND WIRING
Crimping tool
Manufacturer
model No.
Phoenix Contact
CRIMPFOX 6
Co.,Ltd.
Screwdriver