Offset (Temp Offset) Function - SMC Networks HRL400-A 40 Series Operation Manual

Hide thumbs Also See for HRL400-A 40 Series:
Table of Contents

Advertisement

HRX-OM-Z021
Chapter 5 Display and Setting of Various Functions
Operation
Chiller
Stop
Circulating fluid
temperature
"High" Upper
Temperature limit
+2
C
Circulating fluid set
temperature 20ºC
"Low" Lower
temperature limit
-2
C
ON
TEMP READY
signal
OFF
TEMP READY
ON
Alarm (AL12)
OFF
monitoring
Generate
TEMP
READY
No alarm
alarm(AL12)
Status (1): Start operation of the chiller.
Status (2): The temperature is in the "High/Low" range, but no "TEMP READY" signal is generated
since "Ready Time" is set at 300 sec at this point.
Status (3): The 300 sec count for "Ready Time" is reset since the temperature is now outside of the
"Low" range.
Status (4): The 300 sec count for "Ready Time" starts since the temperature is now within the
"High/Low" range.
Status (5): "TEMP READY" signal is generated at this point since the temperature remains in the
"High/Low" range for 300 sec of "Ready Time."
Monitoring of "TEMP READY alarm (AL12)" does not start since "Start Time" is set at 1000
sec.
Status (6): Monitoring of "TEMP READY alarm (AL12)" starts at this point where 1000 sec of "Start
Time" has elapsed.
Status (7): "TEMP READY" signal output continues since the temperature is now back within the "Out
Time" range of 200 sec even though it was temporarily outside the "Low" range.
Status (8): "TEMP READY" signal turns OFF when 200 sec has passed after the temperature rises
above the "High" range. "TEMP READY alarm (AL12)" is simultaneously activated.
Offset
(TEMP OFFSET) function
5.4 Description of the Screen
5-28
1000sec
150sec
(1)
300sec
(2)
(4)
(3)
Fig. 5-6 TEMP READY signal chart
(6)
(7)
(5)
Time
(8)
200sec
100sec
HRL Series