Advertisement

HRX-OM-Q026
Chapter 5
Display and Setting of Various Functions

5.9 Offset Function

5.9.1
Offset function
Offset function
MODE1
MODE2
MODE3
(Default)
5.9 Offset Function
5-22
This is a function that controls the "circulating fluid display temperature" and
the "target temperature for chiller temperature control" by shifting the
temperature for the set offset value.
This product has three different modes of offset functions (MODE 1 to 3).
(The default setting of this function is "OFF".)
See "
Table 5.9-1 Offset function" shown below for these modes.
Refer to "5.9.2 Usage example of offset function" for operation methods.
Refer to "5.9.3 Setting/checking of offset function" for the setting instructions.
[When communication is being used]
The circulating fluid temperature sent by serial communication is the
circulating fluid temperature (the circulating fluid temperature after offset)
which is displayed on the thermo-chiller.
Table 5.9-1 Offset function
Circulating fluid display
Displays the "circulating fluid
discharge temperature".
Displays the temperature that is
"circulating fluid discharge
temperature plus offset temperature".
Displays the temperature that is
"circulating fluid discharge
temperature minus offset
OFF
Displays the "circulating fluid
discharge temperature".
temperature
temperature".
Temperature control
Circulating fluid temperature is
controlled to be "the set circulating
fluid temperature plus offset
temperature".
Circulating fluid temperature is
controlled to be "the set circulating
fluid temperature".
Circulating fluid temperature is
controlled to be "the set circulating
fluid temperature plus offset
temperature".
Circulating fluid temperature is
controlled to be "the set circulating
fluid temperature".