SMC Networks HRL Series Manual

SMC Networks HRL Series Manual

Circulating fluid temperature controller thermo-chiller
Hide thumbs Also See for HRL Series:

Advertisement

Quick Links

Circulating Fluid Temperature Controller
Thermo-chiller
Temperatures for
be controlled individually by one chiller.
Space saving, Reduced wiring
Dual thermo-chiller
HRL200
Energy saving
Power consumption
30
reduced by
%
1 compressor, 1 fan and
2 pumps are controlled by
inverter.
HRL
Series
2 fluid channel systems
Optical system
Cooling capacity [kW]
Temperature stability [°C]
Set temperature range [°C]
1
unit
CH2
To optical system
CH1
To oscillator
power supply
Compressor
Fan
Pump
Dual Channel Refrigerated
Thermo-chiller for Lasers
Laser oscillator
CH2
Oscillator
CH1
Oscillator
CH1
9, 19, 26
±0.1
15 to 25
Footprint
22
%
reduction
One
system for
2 channels
HRSH200
Touch panel
· Numeric keypad inputs
·
Notice for alarms and
maintenance
·
Temperature
waveform
can be displayed.
can
Laser optical
system
Optical system
CH2
1 (Max. 1.5)
±0.5
20 to 40
1
∗1 CH2 ≥ CH1
2
Thermo-chiller
units
To oscillator
To optical
system
HRS012
pp. 5, 15
Numeric keypad display
NAS40-68A

Advertisement

Table of Contents
loading

Summary of Contents for SMC Networks HRL Series

  • Page 1 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Temperatures for 2 fluid channel systems be controlled individually by one chiller. Laser optical system Laser oscillator Optical system Oscillator Oscillator Optical system 9, 19, 26 1 (Max. 1.5) Cooling capacity [kW] Temperature stability [°C] ±0.1...
  • Page 2 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Space saving Reduced wiring/labor Keeping the size similar to the One power supply system for (HRSH series) single chiller, the temperature control of 2 channels temperature of 2 fluid channel Less work-hour for wiring systems are controlled individually.
  • Page 3 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series One compressor controls 2 channels. Temperature of is controlled individually. CH1: Oscillator CH2: Optical system Ventilation Pressure sensor Circulating fluid outlet Temperature sensor Solenoid Inverter Particle filter valve Heat Temperature exchanger...
  • Page 4 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series 3 operation modes of the circulating fluid pump The pump operation mode can be selected by the <Example of the pressure control mode> touch panel. User’s equipment A Operation screen Set values can be entered from the touch panel.
  • Page 5 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Options in demand are standardized. Built-in bypass circuit ( CH1: Oscillator CH2: Optical system (Standard) Inside of the chiller Circulating fluid outlet Particle Bypass valve filters CH2: Optical system Filter Bypass valve CH1: Oscillator...
  • Page 6 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Touch panel p. 15 Improved usability and visibility To status screen To information screen To check operation time screen Home screen Menu screen To software version screen To home screen To temperature waveform To CH1 display screen...
  • Page 7 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Global Supply Network SMC has a comprehensive network in the global market. We now have a presence of more than 500 branch offices and distributors in 83 countries and regions worldwide, such as Asia, Oceania, North/ Central/South America, and Europe.
  • Page 8 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Circulating Fluid Line Equipment Flow Switch Refer to the Web Catalog for details. : Monitors the flow rate and temperature of the circulating fluid 3-Color Display 3-Color Display Digital Flow Switch for PF3W PF2D...
  • Page 9: Table Of Contents

    C O N T E N T S Series Dual Channel Refrigerated Thermo-chiller for Lasers Thermo-chiller Series How to Order/Specifications ............. p. 9 Cooling Capacity ................p. 10 Pump Capacity ................p. 10 Dimensions ..................p. 11 Parts Description ................p. 14 Recommended External Piping Flow ..........
  • Page 10: How To Order/Specifications

    Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series How to Order Cooling capacity Power supply 3-phase 200 VAC (50 Hz) 3-phase 200 to 230 VAC (60 Hz) 9 kW 1 kW 19 kW 1 kW Pipe thread type 26 kW 1 kW Cooling method...
  • Page 11: Cooling Capacity

    Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series ∗1 This is the cooling capacity of the CH1 side when 1 kw heat load is applied to the CH2 side. Cooling Capacity ∗2 Max. 1.5 kW. When 1.5 kW is applied, the cooling capacity of CH1 decreases by 0.5 kW. HRL100-A -20 HRL200-A -20 (CH1)
  • Page 12: Dimensions

    Series Dual Channel Refrigerated Thermo-chiller for Lasers Dimensions HRL100-A -20 Ventilation air inlet Ventilation air inlet Ventilation air outlet 40 or less 330 ±10 1026 Anchor bolt mounting position (View A) For piping port sizes, refer to the “Parts Description” on page 14.
  • Page 13 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Dimensions HRL200-A -20 Ventilation air inlet Ventilation air inlet Ventilation air outlet 40 or less 330 ±10 1026 Anchor bolt mounting position (View A) For piping port sizes, refer to the “Parts Description” on page 14.
  • Page 14 Series Dual Channel Refrigerated Thermo-chiller for Lasers Dimensions HRL300-A -20 Ventilation air inlet Ventilation air inlet Ventilation air outlet 40 or less 1079 330 ±10 1145 1109 Anchor bolt mounting position (View A) For piping port sizes, refer to the “Parts Description” on page 14.
  • Page 15: Parts Description

    Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Parts Description Eye bolt M12 (4 places) Circulating fluid outlet (CH1) Touch panel Handle Handle Bypass valve (CH1) Earth leakage Circulating fluid outlet (CH2) breaker handle Rc1/2 Bypass valve (CH2) Dustproof Fluid fill port (CH1) filter...
  • Page 16: Operation Display Panel

    Series Dual Channel Refrigerated Thermo-chiller for Lasers Operation Display Panel Items shown on the touch panel home screen               Classification CH no. Item Explanation Circulating fluid temperature It indicates the current temperature. ...
  • Page 17: Communication Functions

    Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Communication Functions Contact Input/Output Contact Input/Output, Analog Output Communication Specifications Item Specifications Insulation method Photocoupler Rated input voltage 24 VDC · Run/Stop signal Contact · External switch signal input signal Operating voltage range 21.6 to 26.4 VDC...
  • Page 18 Series Dual Channel Refrigerated Thermo-chiller for Lasers Communication Functions Contact Input/Output, Analog Output Pin Nos. Pin no. Application Division Default setting 24 VDC output Output — 24 VDC input Input — Contact input signal 1 Input Run/Stop ∗ Contact input signal 3 Input Operation mode request signal (fix) ∗...
  • Page 19 Circulating Fluid Temperature Controller Thermo-chiller Dual Channel Refrigerated Thermo-chiller for Lasers Series Communication Functions Serial Communication The following operations can be performed by the serial communication RS-232C/RS-485. Writing Readout To run/stop the product Circulating fluid temperature To change the set value of Circulating fluid pressure circulating fluid temperature Circulating fluid flow rate...
  • Page 20: Optional Accessories

    Series Dual Channel Refrigerated Thermo-chiller for Lasers Optional Accessories Consumables List Part no. Description Qty. Note HRS-S0213 Dustproof filter (Lower) For HRL200-A: 2 pcs. are used per unit. HRS-S0214 Dustproof filter (Upper) For HRL100/200-A: 2 pcs. are used per unit. HRS-S0185 Dustproof filter For HRL300-A: 4 pcs.
  • Page 21: Cooling Capacity Calculation

    Series Cooling Capacity Calculation Required Cooling Capacity Calculation Example 1: When the heat generation amount in the user’s equipment is known. Q: Heat generation The heat generation amount can be determined based on the power consumption or output amount of the heat generating area — i.e. the area requiring cooling — within the user’s equipment. ∗ I: Current User’s equipment...
  • Page 22: Precautions On Cooling Capacity Calculation

    Series Cooling Capacity Calculation Required Cooling Capacity Calculation Example 3: When there is no heat generation, and when cooling the object below a certain temperature and period of time. Heat quantity by cooled substance (per unit time) Q : Unknown [W] ([J/s]) Example of conventional units (Reference) Cooled substance : Water...
  • Page 23: Specific Product Precautions

    Series Specific Product Precautions 1 Be sure to read this before handling the products. Refer to the back cover for safety instructions. For temperature control equipment precautions, refer to the “Handling Precautions for SMC Products” and the “Operation Manual” on SMC website: https://www.smcworld.com Design Operating Environment/Storage Environment...
  • Page 24 Series Specific Product Precautions 2 Be sure to read this before handling the products. Refer to the back cover for safety instructions. For temperature control equipment precautions, refer to the “Handling Precautions for SMC Products” and the “Operation Manual” on SMC website: https://www.smcworld.com Transportation/Carriage/Movement Transportation/Carriage/Movement...
  • Page 25 Series Specific Product Precautions 3 Be sure to read this before handling the products. Refer to the back cover for safety instructions. For temperature control equipment precautions, refer to the “Handling Precautions for SMC Products” and the “Operation Manual” on SMC website: https://www.smcworld.com Mounting/Installation Piping...
  • Page 26 Series Specific Product Precautions 4 Be sure to read this before handling the products. Refer to the back cover for safety instructions. For temperature control equipment precautions, refer to the “Handling Precautions for SMC Products” and the “Operation Manual” on SMC website: https://www.smcworld.com Electrical Wiring Circulating Fluid...
  • Page 27 Series Specific Product Precautions 5 Be sure to read this before handling the products. Refer to the back cover for safety instructions. For temperature control equipment precautions, refer to the “Handling Precautions for SMC Products” and the “Operation Manual” on SMC website: https://www.smcworld.com Operation Restart Time/Operation and Suspension Frequency Caution...
  • Page 28 These safety instructions are intended to prevent hazardous situations and/or Safety Instructions equipment damage. These instructions indicate the level of potential hazard with the labels of “Caution,” “Warning” or “Danger.” They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC) ∗1) and other safety regulations.

This manual is also suitable for: