Download Print this page

Drive Operation - Xylem Bell & Gossett e-80 Series Quick Manual

Hide thumbs Also See for Bell & Gossett e-80 Series:

Advertisement

For safety and correct product usage, read the manual before this product is used.
Position number
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

6 Drive operation

Table 2:
1
Figure 3: Interface screen
Table 3:
Position number
1
2
Name
Digital Input 4
Digital Input 5
10 VDC power supply
Communication Bus 1
Communication Bus 2
Communication Bus 1
Communication Bus 2
Relay 1
Relay 2
2
3 4
5
6
7
8
9
Name
Display
ON/OFF button
Description
Configurable digital input 4, internal pull-
up +24 VDC, contact current 6 mA
Electronic GND
Configurable digital input 4, internal pull-
up +24 VDC, contact current 6 mA
Electronic GND
Power supply +10 VDC, max. 3 mA
Electronic GND
RS485 port 1: RS485-1B N(-)
RS485 port 1: RS485-1A P(+)
RS485 port 1: RS485-COM
RS485 port 2: RS485-2B N(-)
RS485 port 2: RS485-2A P(+)
RS485 port 2: RS485-COM
RS485 port 1: RS485-1B N(-)
RS485 port 1: RS485-1A P(+)
RS485 port 1: RS485-COM
RS485 port 2: RS485-2B N(-)
RS485 port 2: RS485-2A P(+)
RS485 port 2: RS485-COM
Configurable relay 1: normally open
Configurable relay 1: normally closed
Configurable relay 1: common contact
Configurable relay 2: normally open
Configurable relay 2: normally closed
Configurable relay 2: common contact
NOTICE:
For first-time start-up and programming, the unit is equipped with a start-up genie
to select the appropriate operating mode and other parameters for the intended ap‐
plication.
Function
• Start and stop the unit
• Reset the errors by pressing for 5 seconds.
Default setting
Not selected
Not selected
-
Multipump
Modbus
Multipump
Modbus
Error reporting
Motor start
5

Advertisement

loading