Flush welding
socket: installa-
tion
① Metal-peek sealing
The support must be without a gap.
Do not use PTFE (Teflon) tape or similar.
Fixing torque: 15 Nm
T-piece: Installa-
tion
SITRANS LCS100 I/O Link Version
Operating Instructions, 05/2023, A5E52382716-AA
10.4 G 1/2" hygienic process connection/EHEDG approval
② The food contact surface must be
smooth (polished to Ra < 0.8 μm) and
the welding has to be done according to
EHEDG Guidelines 9 and 35.
The sensor should be installed flush with
the process area. The ratio between the
depth of the upstand (L) and the diame-
ter (D-d) of the upstand/Sensor shall be L
/ (D-d) < 1.
If welded adapters are used, the food
contact surface must be smooth (pol-
ished to Ra < 0.8 μm). The welding must
done according to EHEDG Guidelines 9
and 35. Suitable pipe couplings and pro-
cess connections with the applicable
gaskets must be applied according to the
EHEDG Position Paper "Easy cleanable
Pipe couplings and Process connections".
Dimension drawings
75