Fresh Air Supply Requirements; Exhaust Requirements - ADC ML-222 Operator's Manual

Table of Contents

Advertisement

If a closet door is installed: unobstructed air openings are
required. The air openings shall be located 3-inches
(7.62 cm) from the lower opening (above floor level) and
upper opening (below ceiling). The total free area of the air
openings in the door shall not be less than 130 inch
2
(838.708 cm
). Louvered doors with equivalent air openings
are acceptable.
No other fuel-burning appliance shall be installed in the
same closet as the dryer.

Fresh Air Supply Requirements ______

This appliance may only be installed in a room that meets
the appropriate ventilation requirements specified in the
national installation regulations.
When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of
the building. Therefore, the room air must be continually
replenished from the outdoors. If the make-up air is
inadequate, drying time and drying efficiency will be
adversely affected. Ignition problems and sail switch
"fluttering" problems may result, as well as premature motor
failure from overheating. The dryer must be installed with
provisions for adequate combustion and make-up air supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer. Fresh air
ventilation openings shall not be blocked and/or sealed. As
a general rule, an unrestricted air entrance from the outdoors
of 52 inch
2
(335 cm
2
) is required for each dryer. (Based on
1 inch
2
[6.5 cm
2
] per 1,000 Btu [252 kcal].)
A = 11-inches (27.94 cm)
B = 11-inches (27.94 cm)
It is not necessary to have a separate make-up air opening
for each dryer. Common make-up air openings are
acceptable. However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.
EXAMPLE: For a bank of 4 dryers, 2 unrestricted openings
measuring 11-inches by 11-inches (27.94 cm by 27.94 cm)
are acceptable.
To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%. Make-up air openings should not be located in an
area directly near where exhaust vents exit the building.
112217 - 5
Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.
2
IMPORTANT: Make-up air must be free of dry cleaning
solvent fumes. Make-up air that is contaminated by dry
cleaning solvent fumes will result in irreparable damage
to the motors and other dryer components.
NOTE: Component failure due to dry cleaning solvent
fumes will void the warranty.

Exhaust Requirements _______________

Exhaust ductwork should be designed and installed by a
qualified professional. Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by
burner hi-limits, or lint chamber hi-limit protector thermostat.
The dryer must be installed with a proper exhaust duct
connection to the outside.
The design of the flue system shall be such that any
condensate formed when operating the appliance from cold
shall either be retained and subsequently re-evaporated or
discharged.
CAUTION: This dryer produces combustible lint and
must be exhausted to the outdoors.
Improperly sized or installed exhaust ductwork can
create a potential fire hazard.
The ductwork should be laid out in such a way that the
ductwork travels as directly as possible to the outdoors with
as few turns as possible. There should be a minimum
6-inch (15.24 cm) clearance between the back guard and
the first bend in the ductwork for ease of servicing. Single or
independent dryer venting is recommended. It is suggested
that the use of 90° turns be avoided; use 30° and/or 45°
bends instead. The radius of the elbows should preferably
be 1-1/2 times the diameter of the duct. All ductwork should
be smooth inside with no projections from sheet metal
screws or other obstructions, which will collect lint. When
adding ducts, overlap the duct being connected. All ductwork
joints must be taped to prevent moisture and lint from
escaping into the building. Back draft dampers must be
installed in all commonly ducted systems. Inspection doors
should be installed at strategic points in the exhaust
ductwork for periodic inspection and cleaning of lint from
the ductwork.
IMPORTANT: Exhaust back pressure measured by a
manometer/magnehelic in the exhaust duct must be no
less than 0 and must not exceed 0.6 in WC (1.5 mb) with
both tumblers operating.
NOTE: It is recommended that exhaust or booster fans
not be used in the exhaust ductwork system except where
necessary to maintain exhaust back pressure (in the
exhaust duct) between zero and 0.6 in WC with both
tumblers operating. Where employed, booster fans must
not activate the dryer airflow proving switch (sail switch)
when the dryer is not in operation.
When the exhaust ductwork passes through a wall, ceiling,
or roof made of combustible materials, the opening must
be 2-inches (5.08 cm) larger than the duct (all the way
around). The duct must be centered within this opening.
www.adclaundry.com
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad-222

Table of Contents