Table of Content 1. Introduction ..................................2 2. Appearance ..................................2 3. Main Features ................................... 3 4. Set up Instruction ................................4 5. Data Report ..................................5 6. Installation ..................................8 7. Information about Battery Passivation ..........................9 7.1 To determine whether a battery requires activation ....................9 7.2 How to activate the battery ............................
1. Introduction R718B2 is a Wireless 2-Gang Resistance Temperature Detector for Netvox ClassA type devices based on the LoRaWAN open protocol and is compatible with the LoRaWAN protocol. R718B2 connects two external resistance temperature detectors (PT1000) to measures the temperature.
Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne Low power consumption and long battery life Note*: Battery life is determined by the sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html On this website, users can find battery life of various models in different configurations.
4.Set up Instruction On/Off Power on Insert batteries. (users may need a screwdriver to open) Turn on Press and hold the function key for 3 seconds till the green indicator flashes once. Turn off (Restore to factory setting) Press and hold the function key for 5 seconds till green indicator flashes for 20 times. Power off Remove Batteries.
The device report interval will be programmed based on the default firmware which may vary. The interval between two reports must be the minimum time. Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/page/index to resolve uplink data.
Page 8
Example for MinTime/MaxTime logic: Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V MaxTime MaxTime Sleeping(MinTime) Sleeping(MinTime) Wake up and collects data Wakes up and collects data Wakes up and collects data REPORTS 3.6V REPORTS 3.6V REPORTS 3.6V Note: MaxTime=MinTime.
1. The Wireless 2-Gang Resistance Temperature Detector 2. When R718B2 is compared with the last reported (R718B2) has a built-in magnet (see Figure 1 below). When values, the temperature change is exceeded 0.1°C installed, it can be attached to the surface of an object with (default),it will report values at the MinTime interval;...
(if using an electric screwdriver, it is recommended to set the torque as 4kgf) to ensure the device is impermeable. 7. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density.
8. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: • Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely. •...